Sediment Traps

Breathing Hazard - Carbon Monoxide Gas

o High altitude orifice must be installed for operation above 7,700 feet (2,347 m).

-Contact a qualified installer or service agency

Breathing carbon monoxide can cause brain damage or death. Always read and L4nderstand instruction manual

Water heaters covered in this manual have been tested and approved for installation at elevations up to 7,700 feet (2,347 m)

above sea level. For installation above 7,700 feet (2,347m), the water heater's Btu input should be reduced at the rate of 4 percent for each 1,000 feet (305 m) above sea level which

requires replacement of the burner orifice in accordance with

the National Fuel Gas Code ANSI Z22&1/NFPA 54. Contact your local gas supplier for further information.

Failure to replace the standard orifice with the proper high altitude orifice when installed at elevations above 7,700 feet (2,347 m) could result in improper and inefficient operation of

the appliance, producing carbon monoxide gas in excess of the safe limits. This could result in serious injury or death. Contact your local gas supplier for any specific changes that may be required in your area.

Sediment Traps

Fire and Explosion Hazard

"Contaminants in gas lines can cause fire or explosion

Clean all gas piping before installation.

InstaN drip leg in accordance with NFPA 54

Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion. Before attaching the gas line be sure that al! gas pipe is clean on the inside. To trap any dirt or foreign material in the gas

supply line, a drip leg (sometimes called a sediment trap) must be incorporated in the piping. The drip leg must be readily

accessible. Install in accordance with the Gas Piping section. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1INFPA 54.

A sediment trap shall be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. If a tee fitting is used, it shall be installed

in conformance with one of the methods of installation, shown in Figures 19 and 20.

Firs and Explosion Hazard

,Use joint compound or tape corn patible with propane,

Leak test before operating heater.

,Disconnect gas piping and shut-off valve before pressure testi ng syste m.

Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum (Propane [LR]) gases,

The appliance and its gas connection must be leak tested before placing the appliance in operation.

The appliance and its individual shut-off valve shall be

disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5 kPa). It shall be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa).

Connecting the gas piping to the gas control valve of the water

heater can be accomplished by either of the two methods shown in Figures 19 and 20.

GROUND JOINT -

UNION

(OPTIONAL)

CAP

FIGURE 19. GAS PIPING WITH FLEXIBLE CONNECTOR.

CAP

FIGURE 20. GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL.

17

Page 17
Image 17
Kenmore 153336762, 153.336262 Sediment Traps, Fire and Explosion Hazard, •Clean all gas piping before installation