Start Up Conditions

Thermal Expansion

Property Damage Hazard

Avoid water heater damage

It2stallthermal expansion tank if necessary

Contact qualified installer or service agency

Water supply system may, because of such events as high line pressure, frequent cut-offs and the effects of water hammer have installed devices such as pressure reducing valves, check valves, back flow preventers, etc., to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (thermal expansion} and closed systems do not allow for the expansion of heated water.

The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving

point of water heater's temperature-pressure relief valve is

reached, the valve will relief the excess pressure. The

temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank to relieve the pressure built by thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations, see Figure 26.

Thermal Expansion Tank Specifications

 

Tank

Dimensions

Pipe

Model

Capacity

in Inches

Fitting

Number

In Gallons

Diameter

Lenqth

On Tank

153.331020

2

8(203mm)

12-3/4(323mm)

3/4"Male

153.331050

5

11(279mm)

14-3/4(375mm)

3/4"Male

Expansion Tank Sizing Chart

Inlet* Water Heater Capacity (Ganons}

 

Water

 

 

 

 

 

 

Pressure

30

40

50

66

82

Expansion

4Opel

2

2

2

5

5

Tank

50psi

2

2

2

5

5

Capacity

60psi

2

2

5

5

5

Needed

70psi

2

2

5

5

5

 

80psi

2

5

5

5

5

*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air charge. If the inlet water pressure is higher than 40 psi, the expansion tank's air pressure must be adjusted to match that pressure, but must not be higher than 80 psi.

WATER HEATER

(3)

HOT COLD COLD WATERPRESSURE

iNLET FITTINGREDUCING VALVE WITH

BM_PASS

z /

WATER SHUT-OFF

PRESSURE GAUGE INLET COLD

_ECOMMENDED iNSTALLATION

(VERTICAL MOUNTING)

WATER HEATER

COLD WATER

INLET FITT]NG

FLOOR, CEILING JOIST, ETC.

 

PRESSURE

 

REDUCING

 

VALVE WITH

_" (1}

BY-PASS

EXPANSIONTANR

/ t

WATER SHUT-OFF

PRESSURE GAUGEiNLET COLD ALTERNATE RECOMMENDED INSTALLATION

{HORIZONTAL MOUNTING)

FIGURE26.

Strange Sounds

Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not represent harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner

area during heating and cooling periods and should be considered normal. See Condensation section.

Draft Hood Operation

Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the draft hood of the water heater with its burner firing. If the flame

23

Page 23
Image 23
Kenmore 153.33946, 153.33996 Start Up Conditions, Thermal Expansion, Inlet* Water Heater Capacity Ganons Pressure