Installation Instructions (cont'd)

Venting (cont'd)

VENTING SYSTEM EXAMPLE INSTALLATIONS

FOR ALL MODELS

Be sure vent pipe is properlyconnectedto preventescape

AWARNINGofThe vent piping cannot under any circumstances be run down-

dangerousfluegaseswhichcouldcausedeadlyasphyxiation.hill.

AWARNING

Chemical vapor corrosion of the flue and vent system may

occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimn_ing pool chemicals, calcium and sodium chloride, waxes, bleach, and processchemicals are typical compounds which are potentially corrosive.

3" PVC SCHEDULE 40 VENT PIPING

Supplied in the carton with the water heater are:

1.A 3" PVC Schedule 4045 ° vent cap with wire screen.

2.A 3" PVC Schedule 40-90 ° street ell; used to connect the

vent pipe to the water heater when the vent pipe is to be turned horizontally directly off the blower.

3.A 5' section of 3" PVC Schedule 40 pipe (more may be required and must be supplied locally).

3" PVC SCHEDULE 40 90° ELBOW

VENT CAP

WITH SCREEN

I

1. The water heater requires its own (separate) venting system.

2.3" PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for the vent system on all 40 gallon models and 50 gallon 40,000 BTU/HR models.

3.It cannot be connected to existing vent piping or chimney.

4.It must terminate horizontally to the outdoors.

The vent piping can be installed as follows:

1. No more than 3 elbows can be used.

4>

MIN. RISE I/4"

PER FOOT

TOTAL VERTICAL AND

HORIZONTAL RUNS

CANNOT EXCEED 35'

MAX, 3

MIN. RISE I/4"

PER FOOT

MAX 20'

TOTAL VERTICAL AND

HORIZONTAL RUNS

CANNOT EXCEED 35'

MIN. RISE i/4"

PER FOOT

16

Page 16
Image 16
Kenmore 153.335862, L53.335816, 153.335942, 153.335845, 153.335962, 153.335916 Venting contd, Installation Instructions contd

FAQ

What materials are acceptable for the vent system?

3" PVC, ABS or CPVC Schedule 40 piping and fittings are acceptable materials for the vent system on all 40 gallon models and 50 gallon 40,000 BTU/HR models.

Can the water heater share a venting system with other appliances?

No, the water heater requires its own separate venting system.

What is the maximum number of elbows that can be used in the vent piping?

No more than 3 elbows can be used in the vent piping.