6
Drain Requirements
Separate drain P-traps for the sink and dishwasher must be
provided.
Dishwasher drain:
If the dishwasher drain exits through the back wall, the centerline
of the drain pipe must be a minimum of 1/2" (1.3 cm) below the
dishwasher drain. This is required to completely drain the
dishwasher tub so that no standing water remains in tub.
Water Supply Requirements
For dishwasher:
Hot water line with 20-120 psi (138-827 kPa) water pressure.
120°F (49°C) water at dishwasher.
Copper tubing with compression fitting. 3/8" O.D. is
recommended.
A 90° elbow with 3/8" N.P.T. external pipe threads on one end.
IMPORTANT:Do not solder within 6" (15.2 cm) from water inlet
valve.
For sink faucet:
Hot and cold water line.
Copper tubing with compression fittings for specific faucet to
be installed.
Electrical Requirements
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
Do not ground to a gas pipe.
22-1/32"
(56.0 cm)
to bottom of
dishwasher drain
1/2" (1.3 cm)
minimum
back wall
Check with a qualified electrician if you are not sure the
dishwasher is properly grounded.
Do not have a fuse in the neutral or ground circuit.
A 120-volt, 60 Hz, AC-only, 15 or 20 amp fused electrical
supply is required. (Circuit breaker or time-delay fuse is
recommended.) It is recommended that a separate circuit
serving only this appliance be provided.
Hot Water Accessory Tank
If you plan to install the Hot Water Accessory Tank Part
No. 4396282, an additional separate120-volt, 60 Hz, AC-only, 15
or 20 amp fused electrical supply is required.
Garbage Disposer
If you plan to install a garbage disposer, an additional separate
120-volt, 60 Hz, AC-only, 15 or 20 amp fused electrical supply is
required.
Recommended ground method
For your personal safety, this appliance must be grounded. This
appliance is equipped with a power supply cord having a 3 prong
ground plug. To minimize possible shock hazard, the cord must
be plugged into a mating 3 prong ground-type outlet, grounded in
accordance with local codes and ordinances.
If a mating outlet is not available, it is the personal responsibility
and obligation of the customer to have a properly grounded
3 prong outlet installed by a qualified electrician.

If dishwasher must be direct wired

Use flexible, armored or non-metallic sheathed, copper wire
with grounding wire that meets the wiring requirements for
your home and local codes and ordinances.
Use a CSA-certified, U.L.- or C-U.L.-listed conduit connector
or if using non-metallic sheathed, copper wire, a CSA-
certified, U.L.- or C-U.L.-listed cable clamp connector.
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
WARNING
WARNING
Electrical Shock Hazard
Electrically ground dishwasher.
Connect ground wire to green ground connector in
terminal box.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.