KitchenAid KSBN220SSS Outdoor Side Burner Installation, Installation Instructions

Models: KSBN220SSS

1 12
Download 12 pages 21.32 Kb
Page 6
Image 6
Line pressure testing:

Line pressure testing:

Testing above 1/2 psi (3.5 kPa) or 14 inches (35.5 cm) W.C. (gauge):

The side burner and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures greater than 1/2 psig (3.5 kPa).

Testing below 1/2 psi (3.5 kPa) or 14 inches (35.5 cm) W.C. (gauge) or lower:

The side burner must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

INSTALLATION INSTRUCTIONS

Outdoor Side Burner Installation

Natural Gas:

WARNING

Excessive Weight Hazard

Failure to do so can result in back or other injury.

Natural Gas:

Side burners are equipped for use with Natural gas. They are design-certified by CSA International for L.P. (propane or butane) gases with appropriate conversion.

Side burners are set for natural gas use and have a pressure regulator with 1/2female pipe threads.

rear of side

burner1/2side burner gas pipe

flexible gas connector

The supply line shall be equipped with an approved shutoff valve. This valve should be located in the same area as the side burner and should be in a location that allows ease of opening and closing. Do not block access to the shutoff valve. The valve is for turning on or shutting off gas to the appliance.

shutoff valve “open” position

gas supply line INSTALLATION INSTRUCTIONS

to side burner

L.P. gas conversion from a local L.P. gas supply:

Conversion must be made by a qualified person. A qualified natural gas technician shall provide the L.P. gas supply to the selected side burner location in accordance with the National Fuel Gas Code NFPA 54 and local codes.

To convert to L.P. gas, the L.P. Gas Conversion Kit No. 4396311 must be used. Follow Instructions included with kit.

L.P. gas conversion using an L.P. fuel tank:

To convert to L.P. gas, the L.P. Gas Conversion Kit

No. 4396311 must be used. Follow Instructions included with kit.

An L.P. gas cylinder, not larger than 20 pounds, must be purchased separately.

This installation must conform with local codes and ordinances. In the absence of local codes, installations must conform with either the National Fuel Gas Code ANSI Z223.1, or CAN/CGA- B149.1 Natural Gas and Propane installation code.

1.Place side burner into outdoor enclosure, but leave enough room in back to connect to gas supply.

Copies of the standards listed may be obtained from:

CSA International

8501 East Pleasant Valley Rd.

Cleveland, Ohio 44131-5575

WARNING

Explosion Hazard

Use a new CSA International approved “outdoor” gas supply line.

Securely tighten all gas connections.

If connected to LP, have a qualified person make sure gas pressure does not exceed 11” (28 cm) water column.

Examples of a qualified person include:

licensed heating personnel,

authorized gas company personnel, and authorized service personnel.

Failure to do so can result in death, explosion, or fire.

2. Make gas connections.

A combination of pipe fittings must be used to connect the outdoor side burner to the existing gas line.