Kohler 8.5RES, 12RES manual Continuous Power Mode, 2.4.1Resetting Controller after a Fault Shutdown

Models: 12RES 8.5RES

1 36
Download 36 pages 14.59 Kb
Page 18
Image 18

Code

Fault

Description

Check

HB

High battery

Fault code is displayed if the engine starting battery voltage rises

Check the battery rating and condition.

 

voltage warning

above 16 VDC for a 12 VDC system or above 30 VDC for a

 

 

 

24 VDC system for more than 10 seconds when the engine is not

Check the battery charger operation.

 

 

running. This fault condition does not inhibit engine starting.

 

 

 

 

 

The fault condition clears when the battery voltage returns to a

 

 

 

voltage within the limits for more than 10 seconds.

 

 

 

 

 

LB

Low battery

Fault code is displayed if the engine starting battery voltage falls

Check the battery rating and condition.

 

voltage warning

below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC

Check the battery charger operation.

 

 

system for more than 10 seconds when the engine is not running.

 

 

 

 

 

This fault condition does not inhibit engine starting.

Charge or replace the battery.

 

 

The fault condition clears when the battery voltage returns to a

 

 

 

voltage within the limits for more than 10 seconds.

 

Figure 2-4 ADC 2100 Fault Warning Codes

2.4.1Resetting Controller after a Fault Shutdown

Always identify and correct the cause of a fault shutdown before resetting the controller. Use the following procedure to reset the generator set controller after a fault shutdown.

1.Move the generator set master switch to OFF/RESET.

7.Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.

Note: The controller’s LED display remains off until an engine start command is received.

Opening and closing a remote start/stop contact also resets the controller.

2.5 Continuous Power Mode

2.Disconnect the generator set from the load using the line circuit breaker or ATS. See the safety precautions at the beginning of this section before proceeding.

3.Identify and correct the cause of the fault shutdown. See the safety precautions at the beginning of this section before proceeding. Refer to Section 4, Troubleshooting.

4.Start the generator set by moving the generator set master switch to RUN. Test operate the generator set to verify that the cause of the shutdown has been corrected.

5.Move the generator set master switch to OFF/RESET.

6.Reconnect the generator set to the load using the line circuit breaker or ATS.

The ADC 2100 is powered by the generator set engine starting battery. A jumper on the back of the controller maintains power to the controller at all times. Controllers are shipped with the jumper connected.

Note: The 8.5 and 12 RES generator sets are equipped with factory-installed battery chargers to prevent battery discharge.

Disconnecting the jumper allows the controller to power down automatically 48 hours after the generator set shuts down if the generator set master switch is in the AUTO position. A remote start signal (from a transfer switch or a remote start/stop switch connected to controller leads 3 and 4) or moving the generator set master switch to the RUN position turns the controller back on.

Contact an authorized distributor/dealer to disconnect the jumper, if necessary.