3.3 Lubrication System

See Section 3.2, Service Schedule, for oil change and oil filter replacement intervals. See Section 1.5, Service Views, for the oil drain, oil check, oil fill, and oil filter locations.

For extended operation, check the oil level every 8 hours. Maintain the oil level at or near, not over, the full mark on the dipstick.

3.3.1Low Oil Pressure Shutdown

The low oil pressure shutdown feature protects the engine against internal damage if the oil pressure drops below 24.1 kPa ±13.8 kPa (3.5 psi ±1.5 psi) because of oil pump failure or other malfunction. The shutdown feature does not protect against damage caused by operating with the oil level below the safe range; it is not a low oil level shutdown. Check the oil level regularly, and add oil as needed.

3.3.2Oil Check

The generator set is shipped with oil. Before operating a new generator set, check the engine oil in the

crankcase. See Section 1.5, Generator Set Components. Verify that the oil level is at the F mark on the dipstick. Add oil that has a viscosity appropriate for

the climate. See Section 3.3.3, Engine Oil Recommendation.

Do not check the oil level when the generator set is running. Shut down the generator set and wait several minutes before checking the oil level.

3.3.3Engine Oil Recommendation

Use API (American Petroleum Institute) Service Class SG, SH, or SJ synthetic oil. Synthetic oil oxidizes and thickens less than other oils and leaves the engine intake valves and pistons cleaner. Select the viscosity based on the air temperature at the time of operation. See Figure 3-1.

10W-30

5W-20, 5W-30

°F --20

0

20 32 40

60

80

100

°C --30 --20

--10

0

10 20

30

40

Temperature

Range Expected Before Next Oil Change

Figure 3-1 Engine Oil Selection

3.3.4Oil Change Procedure

Drain the oil while it is still warm.

1.Drain the oil.

a.Place the generator set master switch in the OFF position.

b.Disconnect the power to the battery charger.

c.Disconnect the generator set engine starting battery, negative (--) lead first.

d.Remove the housing side panel.

e.Remove the oil drain hose from its retaining clip. Remove the cap from the oil drain hose and lower the hose into an oil collection container.

f.Open the oil drain valve on the engine.

g.Allow time for the engine oil to drain completely.

h.Close the oil drain valve.

i.Replace the cap on the oil drain hose. Replace the oil drain hose in its retaining clip.

2.Replace the oil filter.

a.Remove the oil filter by rotating it counterclockwise with an oil filter wrench.

TP-6331 5/04

Section 3 Scheduled Maintenance 11

Page 23
Image 23
Kohler 12RES Lubrication System, Low Oil Pressure Shutdown, Oil Check, Engine Oil Recommendation, Oil Change Procedure

12RES, 8.5RES specifications

The Kohler 8.5RES and 12RES generators are known for their robust reliability and efficiency, making them ideal solutions for both residential and light commercial applications. These generators are equipped with advanced technologies that ensure seamless power delivery during outages, giving users peace of mind.

The Kohler 8.5RES, with its 8.5 kW output, is perfect for homeowners who require backup power for essential appliances and systems. It efficiently powers refrigerators, lights, and heating or cooling systems, providing convenience when the grid is down. The 12RES, delivering 12 kW, caters to larger homes or small businesses, accommodating additional loads such as sump pumps and electric dryers.

One of the standout features of these generators is the Kohler Command PRO engine, designed for maximum performance and longevity. This engine operates with low noise levels, ensuring that any power interruption goes unnoticed. Both models come with an innovative digital control panel that simplifies operation and monitoring, allowing users to access critical information at a glance.

The Kohler 8.5RES and 12RES are equipped with the patented Automatic Voltage Regulation (AVR) technology. This feature maintains a steady voltage output to protect sensitive electronics from damage caused by power surges. The modular design of these units facilitates easy maintenance, with service intervals and replacement parts readily available.

For eco-conscious consumers, the Kohler generators meet EPA emission regulations, ensuring a cleaner energy solution. The units also offer a comprehensive sound-attenuated enclosure, resulting in quieter operation, making them suitable for use in suburban environments.

Installation is straightforward, with various connection options for natural gas and propane fueling. Both models come with a fully automatic transfer switch, providing seamless transition from grid to generator power. This ensures that critical systems are always operational during outages.

In summary, the Kohler 8.5RES and 12RES generators stand out for their reliability, advanced technology, and user-friendly features. Their powerful engines, efficient performance, and low emissions make them an excellent choice for anyone looking to invest in a dependable backup power solution. Whether for home use or light commercial needs, these generators provide the essential peace of mind that comes with knowing you have power when you need it most.