Kohler 8.5RES Circuit Protection, Storage Procedure, Line Circuit Breaker, Fuses, Fuel System

Models: 12RES 8.5RES

1 36
Download 36 pages 14.59 Kb
Page 28
Image 28

3.10 Circuit Protection

If the generator set circuit breaker trips or the fuses blow repeatedly, see Section 4, Troubleshooting, for possible causes.

3.10.1 Line Circuit Breaker

A line circuit breaker interrupts the generator output in the event of a fault in the wiring between the generator and the load. The line circuit breaker location is shown in Figure 1-1. See Figure 3-8 for the circuit breaker ratings. If the circuit breaker trips, reduce the load and switch the breaker back to the ON position. With the breaker in the OFF position the generator set runs but the generator output is disconnected from the load.

 

Circuit Breaker

Model

Rating, Amps

 

 

8.5RES

40

 

 

12RES

50

Figure 3-8 Line Circuit Breakers

3.10.2 Fuses

The engine harness contains two 10-amp and one 20-amp inline fuses. See Figure 3-9. Another 10-amp fuse protects the battery charger.

Always identify and correct the cause of a blown fuse before restarting the generator set. Refer to Section 4, Troubleshooting, for conditions that may indicate a blown fuse. Replace blown fuses with identical replacement parts.

 

 

Part

 

Fuse

Label

Number

Location

 

 

 

 

Auxiliary winding

F1

292937

Lead 55

 

 

 

 

Relay interface

F2

223316

Lead PF2

board

 

 

 

 

 

 

 

Controller

F3

223316

Lead PF1

 

 

 

 

Battery charger

AGS 10

Battery charger DC

 

 

 

lead. See Section 2.6.

Figure 3-9 Fuses

3.11 Storage Procedure

Perform the following storage procedure before removing the generator set from service for three months or longer. Follow the engine manufacturer’s recommendations for storage, if available.

Note: Run the generator set monthly whenever possible.

3.11.1 Lubricating System

1.Operate the generator set until it reaches operating temperature, or about 15 minutes.

2.Stop the generator set.

3.While the engine is still warm, drain the engine lubrication oil from the engine crankcase.

4.Refill the engine crankcase with oil. See Section 3.3.3 for oil recommendations.

5.Run the generator set for a few minutes to distribute the clean oil.

6.Stop the generator set.

3.11.2 Fuel System

1.Start the generator set.

2.With the generator set running, shut off the gas supply.

3.Run the generator set until the engine stops.

4.Place the generator set master switch in the OFF/RESET position.

16 Section 3 Scheduled Maintenance

TP-6331 5/04

Page 28
Image 28
Kohler 8.5RES, 12RES Circuit Protection, Storage Procedure, Line Circuit Breaker, Fuses, Lubricating System, Fuel System