3.10 Circuit Protection
If the generator set circuit breaker trips or the fuses blow repeatedly, see Section 4, Troubleshooting, for possible causes.
3.10.1 Line Circuit Breaker
A line circuit breaker interrupts the generator output in the event of a fault in the wiring between the generator and the load. The line circuit breaker location is shown in Figure
| Circuit Breaker |
Model | Rating, Amps |
|
|
8.5RES | 40 |
|
|
12RES | 50 |
Figure
3.10.2 Fuses
The engine harness contains two
Always identify and correct the cause of a blown fuse before restarting the generator set. Refer to Section 4, Troubleshooting, for conditions that may indicate a blown fuse. Replace blown fuses with identical replacement parts.
|
| Part |
|
Fuse | Label | Number | Location |
|
|
|
|
Auxiliary winding | F1 | 292937 | Lead 55 |
|
|
|
|
Relay interface | F2 | 223316 | Lead PF2 |
board |
|
|
|
|
|
|
|
Controller | F3 | 223316 | Lead PF1 |
|
|
|
|
Battery charger | — | AGS 10 | Battery charger DC |
|
|
| lead. See Section 2.6. |
Figure
3.11 Storage Procedure
Perform the following storage procedure before removing the generator set from service for three months or longer. Follow the engine manufacturer’s recommendations for storage, if available.
Note: Run the generator set monthly whenever possible.
3.11.1 Lubricating System
1.Operate the generator set until it reaches operating temperature, or about 15 minutes.
2.Stop the generator set.
3.While the engine is still warm, drain the engine lubrication oil from the engine crankcase.
4.Refill the engine crankcase with oil. See Section 3.3.3 for oil recommendations.
5.Run the generator set for a few minutes to distribute the clean oil.
6.Stop the generator set.
3.11.2 Fuel System
1.Start the generator set.
2.With the generator set running, shut off the gas supply.
3.Run the generator set until the engine stops.
4.Place the generator set master switch in the OFF/RESET position.
16 Section 3 Scheduled Maintenance |