Hearth Protection
The floor protector must be a
Stove Base
| ||
(98mm) | Firebox Front Edge | (98mm) |
|
| |
6” | Hearth Protection | 6” |
(152mm) | (152mm) | |
| 6” |
|
Figure 9 | (152mm) |
|
Minimum Size Hearth Protection
(245mm) | (362mm) | (245mm) |
(273mm)
| Outline of Stove Base |
|
|
|
28” |
|
|
| |
| ||||
(711mm) |
|
| ||
| (225mm) | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(213mm)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| (467mm) |
|
|
|
| |||||||
|
|
|
| (192mm) |
|
|
|
|
|
|
| (192mm) |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Figure 10 |
|
|
| (851mm) |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Vent Termination Requirements
1.Do not terminate the vent in any enclosed or
2.Vent surfaces can become hot enough to cause burns if touched.
3.Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be installed outside when the stove is vented directly through a wall. This will create a natural draft to prevent the pos- sibility of smoke or odor during appliance shut down or power failure and avoid exposing people or shrubs to high temperatures.
4.The vent should terminate no less than four feet below, no less than four feet horizontally from, and no less than one foot above doors and windows, or gravity/ventilation air inlets into the building.
5.The distance between the bottom of termination and grade should be a minimum of 12” (305mm). The distance be- tween the bottom of the termination and a public walkway should be a minimum of seven feet.
6.Locate the vent termination at least two feet away from combustible materials such as shrubs, plants, grass, fences, roof overhangs, and adjacent buildings.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.