Lennox International Inc EL180UHE Vent Connection Upflow And Horizontal Position

Models: EL180UHE

1 32
Download 32 pages 29.07 Kb
Page 15
Image 15
VENT CONNECTION UPFLOW AND HORIZONTAL POSITION

VENT CONNECTION UPFLOW AND HORIZONTAL POSITION

 

“DISCONNECTED VENT”

 

WARNING

 

STICKER

 

VENT PIPE

 

(min. 6” length)

 

“DISCONNECTED VENT”

 

WARNING

 

STICKER

 

FLUE TRANSITION

 

COLLAR

 

 

FLUE

VENT PIPE

TRANSITION

COLLAR

(min. 6” length)

FIGURE 22

Common Venting Using Metal-Lined Masonry Chimney

 

 

SEALED

 

MAX. LENGTH

 

 

-- SEE NOTE 1

 

5 ft. (1.5 m)

BELOW.

 

MIN. LENGTH -- AS

 

minimum

EXTERIOR

SHORT AS PRACTICAL

 

CHIMNEY WITH

 

 

 

 

METAL

 

 

LINER

VENT CONNECTOR

 

4 in. (102 mm)

 

 

minimum

 

 

 

FURNACE

 

OTHER

 

 

APPLIANCE

 

 

 

PERMANENTLY

 

 

SEALED FIREPLACE

 

 

OPENING

NOTE 1 - Refer to the provided venting tables for installations. Refer to the capacity requirements shown in the provided venting tables.

FIGURE 23

Manual backgroundWARNING

Asphyxiation hazard. The exhaust vent for this fur­ nace must be securely connected to the furnace flue transition at all times.

DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose gran­ ular insulating material.

Manual backgroundIMPORTANT

SINGLE appliance venting of a fan‐assisted furnace into a tile‐lined masonry chimney (interior or outside wall) is PROHIBITED. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized ac­ cording to the provided venting tables and the vent pipe manufacturer's instructions.

A fan-assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:

SThe chimney is currently serving at least one drafthood- equipped appliance;

SThe vent connectors and chimney are sized according to the provided venting tables.

If type B1 double‐wall vent is used inside a chimney, no oth­ er appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof as­ sembly according to the terms of their respective listings and the vent manufacturer's instructions.

When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting EL180UHE series units. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney. Never connect a Category I appliance to a chimney that is servicing a solid-fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed.

Page 15

Page 15
Image 15
Lennox International Inc EL180UHE installation instructions Vent Connection Upflow And Horizontal Position