| HEAT FAN‐OFF TIME IN SECONDS |
|
|
| |||||||||
|
|
|
|
| NO JUMPER |
|
|
|
|
|
|
|
| ||
| To adjust |
| |||||||||||||
|
|
|
|
| achieve desired setting. |
|
|
|
| ||||||
60 Second | 90 Second | 120 Second | 180 Second | ||||||||||||
off Time | off Time |
| off Time |
| off Time | ||||||||||
60 | 90 | 120 | 180 | 60 | 90 | 120 | 180 | 60 | 90 | 120 | 180 | 60 | 90 | 120 | 180 |
FIGURE 32
Constant Torque Motor
EL180UHE units are equipped with a constant torque ECM motor. It has a DC motor coupled to an electronic control module both contained in the same motor housing. The mo tor is programmed to provide constant torque at each of the five selectable speeds. The motor has five speed taps. Each tap requires 24 volts to energize.
Input Voltage Requirements
The circuit is designed to be operated with AC voltage. A voltage of 12 to 33VAC is required to energize the motor. Expected current draw will be less than 20mA.
Blower Speeds
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace.
2 - Remove blower access panel.
3 - Disconnect existing speed tap at integrated control speed terminal.
NOTE - Termination of any unused motor leads must be insulated.
4 - Place unused blower speed tap on integrated control “PARK” terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring dia gram for desired heating or cooling speed. See Product Specifications manual for blower performance data.
6 - Connect selected speed tap at integrated control speed terminal.
7 - Resecure blower access panel.
8 - Turn on electrical power to furnace.
9 - Recheck temperature rise.
Electronic Ignition
The integrated control has an added feature of an internal Watchguard control. The feature serves as an automatic re set device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line
pressure. After one hour of continuous thermostat demand for heat, the Watchguard will
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous opera tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to dis connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, a qualified techni cian should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju ry or death.
Filters
All EL180UHE filters are installed external to the unit. Fil ters should be inspected monthly. Clean or replace the fil ters when necessary to ensure that the furnace operates properly. Replacement filters must be rated for high veloc ity airflow. Table 1 lists recommended filter sizes.
Flue And Chimney
1 - Check flue pipe, chimney and all connections for tight ness and to make sure there is no blockage.
2 - Check unit for proper draft.
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC + 10%.
3 - Check
Unit Nameplate__________Actual__________
Cleaning the Burners
NOTE - Use papers or protective covering in front of the fur nace during cleaning.
1 - Turn off both electrical and gas power supplies to fur nace.
Page 29