HORIZONTAL RIGHT POSITION
Top Vent Discharge
Vent Pipe
Pressure Switch
Flue
Transition
Cover Plate
AIR
FLOW | Collector Box |
DGas supply piping must be brought into the unit from the bot tom in order to accommodate the flue pipe.
DCut combustion air inducer tubing from 9” to 8” to avoid inter ference with inducer motor
DRemove
D
FIGURE 20
HORIZONTAL RIGHT POSITION |
Side Vent Discharge - no modifications necessary |
Pressure Switch |
Vent Pipe |
AIR |
FLOW |
Flue Transition |
Collector Box |
FIGURE 21
The EL180UHE series units are classified as
nace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger. The EL180UHE is not approved for use with horizontal venting. NOTE - Use these instructions as a guide. They do not su persede local codes. This furnace must be vented accord ing to all local codes these installation instructions, and the provided venting tables in these instructions
The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper ap plication, termination, construction and location of vents must conform to local codes having jurisdiction. In the ab sence of local codes, the NFGC serves as the defining doc ument.
Use
Install the first vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet. See figure 22.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central fur naces must be either tile‐lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See figures 23 and 24 for com mon venting.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not
Insulation for the flexible vent pipe must be an encapsu lated fiberglass sleeve recommended by the flexible vent pipe manufacturer. See figure 23.
Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.
IMPORTANT
Once the venting system is installed, attach the “Dis connected Vent” warning sticker to a visible area of the plenum near the vent pipe. See figure 22. The warning sticker is provided in the bag assembly. Or der kit 66W04 for additional stickers.
Page 14