Lennox International Inc EL180UHE installation instructions Setting Equipment, Upflow Applications

Models: EL180UHE

1 32
Download 32 pages 29.07 Kb
Page 8
Image 8
Setting Equipment

Setting Equipment

Upflow ApplicationsWARNING

Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur­ nace. Doing so will adversely affect the operation of the safety control devices, which could result in per­ sonal injury or death.

The EL180UHE gas furnace can be installed as shipped in either the upflow position or the horizontal position. Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610

mm)at unit front]. The unit must be level.

NOTE - Units with 1/2 or 3/4 hp blower motors are equipped with three flexible legs and one rigid leg. See figure 6. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer

must be removed before the furnace is placed into op­

eration. After the bolt and washer have been removed, the

rigid leg will not touch the blower housing.

Units with 1/2 or 3/4 HP Blower Motor

RIGID LEG

remove shipping bolt and washer

FIGURE 6

Upflow Applications

Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­ cove installations are shown in figure 7.

Upflow Application Installation Clearances

 

Top

 

Left Side

 

Right Side

 

Bottom

 

Type of Vent

Type C

Type B1

Connector

 

 

Top

1 in. (25 mm)

1 in. (25 mm)

*Front

2-1/4 in. (57 mm)**

2-1/4 in. (57 mm)

 

 

 

Back

0

0

 

 

 

Sides

0

0

 

 

 

Vent

6 in. (152 mm)

1 in. (25 mm)

 

 

 

Floor

0

0

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4-1/2” if single wall vent pipe is used.

For installation on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

Left side requires 3 inches if a single wall vent is used on 14-1/2 inch cabinets, or 2 inches if a single wall vent pipe is used on 17-1/2 inch cabinets.

FIGURE 7

Page 8

Page 8
Image 8
Lennox International Inc EL180UHE installation instructions Setting Equipment, Upflow Applications