Lennox International Inc EL180UHE Removing the Bottom Panel, Horizontal Applications

Models: EL180UHE

1 32
Download 32 pages 29.07 Kb
Page 10
Image 10
Removing the Bottom Panel

Removing the Bottom Panel

Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See figure 10.

Removing the Bottom Panel

Screw

Bottom Cap

Bottom Panel

FIGURE 10

 

Horizontal Application

 

 

 

Installation Clearances

 

 

 

Top

 

 

Left

 

FLOW

Right

 

AIR

End

 

 

End

 

Bottom

 

 

Vent Connector

Type C

 

Type B1

Type

 

 

 

 

Top

0

 

0

*Front

2-1/4 in. (57 mm)**

 

2-1/4 in. (57 mm)

Back

0

 

0

Ends

2 in. (51 mm)

2 in. (51 mm)

 

 

 

Vent

6 in. (152 mm)

1 in. (25 mm)

 

 

 

Floor

0

0

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4-1/2 in. if single wall vent pipe is used.

For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 11

Horizontal Applications

The EL180UHE furnace can be installed in horizontal ap­ plications. Order horizontal suspension kit (51W10) from Lennox, or use equivalent suspension method.

Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­ cove installations are shown in figure 11.

This furnace may be installed in either an attic or a crawl­ space. Either suspend the furnace from roof rafters or floor joists, as shown in figure 12, or install the furnace on a platform, as shown in figure 13.

Typical Horizontal Application

Unit Suspended in Attic or Crawlspace

Metal

Strap

Bracket

3/16”

Air

Flow

FIGURE 12

NOTE - Heavy-gauge perforated sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust pip­ ing installation. Cooling coils and supply and return air plenums must be supported separately.

NOTE - When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain.

Return Air -- Horizontal Applications

Return air must be brought in through the end of a furnace installed in a horizontal application. The furnace is equipped with a removable bottom panel to facilitate installation. See figure 10.

Page 10

Page 10
Image 10
Lennox International Inc EL180UHE Removing the Bottom Panel, Return Air --Horizontal Applications