Lennox International Inc EL180UHE Gas Piping, Removal of the Furnace from Common Vent, Gas Supply

Models: EL180UHE

1 32
Download 32 pages 29.07 Kb
Page 20
Image 20
Removal of the Furnace from Common Vent

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a venting system commonly run with separate gas ap­ pliances, the venting system is likely to be too large to properly vent the remaining attached appliances.

Conduct the following test while each appliance is operat­ ing and the other appliances (which are not operating) re­ main connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting re­ quirements section.

Gas Piping WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon mon­ oxide poisoning or death.

The following steps shall be followed for each ap­ pliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1 - Seal any unused openings in the common venting sys­ tem.

2 - Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.

3 - Close all building doors and windows and all doors be­ tween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dry­ ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper­ ate at maximum speed. Do not operate a summer ex­ haust fan. Close fireplace dampers.

4 - Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.

5 - After the burner have operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle.

6 - After determining that each appliance connected to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace damp­ ers, and any other gas-burning appliances to their pre­ vious mode of operation.

7 - If a venting problem is found during any of the preced­ ing tests, the common venting system must be modi­ fied to correct the problem.

Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan­ dards of the National Fuel Gas Code ANSI Z223.1.

Gas Piping

Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.

Gas SupplyCAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

Gas Supply

1 - This unit is shipped standard for left or right side instal­ lation of gas piping (or top entry in horizontal applica­ tions). Connect the gas supply to the piping assembly.

2 - When connecting the gas supply piping, consider fac­ tors such as length of run, number of fittings, and fur­ nace rating to avoid excessive pressure drop. Table 6 lists recommended pipe sizes for typical applications.

3 - The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.

4 - The piping should be sloped 1/4 inch (6.4 mm) per 15 feet (4.57 m) upward toward the meter from the fur­ nace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang­ ers or straps. Install a drip leg in vertical pipe runs to the unit.

5 - A 1/8” N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See figure 31.

6 - In some localities, codes may require the installation of a manual main shut‐off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.

Manual backgroundIMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petro­ leum gases.

NOTE - If emergency shutoff is necessary, shut off the main manual gas valve and disconnect main power to the fur­ nace. The installer should properly label these devices.

Page 20

Page 20
Image 20
Lennox International Inc EL180UHE installation instructions Gas Piping, Removal of the Furnace from Common Vent, Gas Supply