Lennox International Inc EL280UH Troubleshooting Heating Sequence of Operation, Page

Models: Elite Series Gas Furnace Upflow/Horizontal Air Discharge EL280UH

1 51
Download 51 pages 39.91 Kb
Page 44
Image 44
Troubleshooting: Heating Sequence of Operation

Troubleshooting: Heating Sequence of Operation

HEATING SEQUENCE OF OPERATION

NORMAL AND ABNORMAL HEATING MODE

POWER ON

CONTROL SELF−CHECK OKAY?

POLARITY OKAY?

YES

IS THERE A

PROPER GROUND?

YES

 

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

 

 

INDOOR BLOWER OFF. (RESET CONTROL BY

 

 

 

 

 

 

TURNING MAIN POWER OFF.)

 

 

 

 

 

 

 

 

 

 

 

 

NO

POLARITY REVERSED.

 

 

 

 

 

STATUS ERROR CODE 5 + 4.

 

 

 

 

 

 

 

 

 

NO

 

 

 

SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.

 

 

STATUS ERROR CODE 5 + 3.

 

 

 

 

NO

A

NORMAL OPERATION:

STATUS LED −− PULSE

B

THERMOSTAT CALLS FOR HEAT:

STATUS LED −− HEARTBEAT

YES

PRIMARY AND SECONDARY LIMIT

SWITCHES CLOSED?

YES

ROLLOUT SWITCH CLOSED?

YES

FIRST (LOW) STAGE PRESSURE SWITCH

CONTACTS OPEN?

YES

SECOND (HIGH) STAGE PRESSURE SWITCH

CONTACTS OPEN?

YES

COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER ON. HAS PRIMARY OR

SECONDARY LIMIT RESET WITHIN 3 MINUTES?

STATUS ERROR CODE 3 + 1.

 

 

NO

 

NO

 

 

 

 

 

 

 

 

60−MINUTE LIMIT WATCHGUARD MODE.

 

 

GAS VALVE OFF, COMBUSTION AIR INDUCER

 

 

OFF, INDOOR BLOWER OFF WITH DELAY.

 

 

STATUS ERROR CODE 4 + 5.

 

 

 

 

 

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

 

INDOOR BLOWER ON.

 

 

 

 

STATUS ERROR CODE 5 + 1.

 

 

SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS

NO

 

RESET AND MAIN POWER IS INTERRUPTED OR

T’STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.

 

 

 

 

 

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF. CONTROL REMAINS UNTIL PRESSURE SWITCH IS DETECTED OPEN. STATUS ERROR CODE 2 + 4

NO

YES

NO

YES

TWO−STAGE OR SINGLE−STAGE THERMOSTAT

CALL FOR HEAT

COMBUSTION AIR INDUCER ON LOW SPEED.

1STATUS LED −− HEARTBEAT

GAS VALVE OFF.

COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF.

CONTROL WILL NOT ATTEMPT SECOND−STAGE

OPERATION DURING THIS HEAT DEMAND.

FIRST−STAGE OPERATION WILL BE ATTEMPTED.

STATUS ERROR CODE 2 + 6.

CONTINUED ON NEXT PAGE

1If the furnace is operating on continuous fan mode (terminals

air inducer will energize on high speed, the gas valve will energize on second−stage heat and the furnace

will operate on high fire. Furnace will stay on high fire 60 seconds then switch to low fire.

Page 44

Page 44
Image 44
Lennox International Inc EL280UH Troubleshooting Heating Sequence of Operation, Heating Sequence Of Operation, Page