Setting Equipment

Setting Equipment

Manual backgroundWARNING

Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the fur- nace. Doing so will adversely affect the operation of the safety control devices, which could result in per- sonal injury or death.

The EL280UH gas furnace can be installed as shipped in either the upflow position or the horizontal position. Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610

mm)at unit front]. The unit must be level.

NOTE − Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. See figure 7. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must be removed before the furnace is placed into opera- tion. After the bolt and washer have been removed, the rig- id leg will not touch the blower housing.

EL280UH090P48B and

EL280UH110P48C with 1/2 HP

BLOWER MOTOR

Manual backgroundManual background RIGID LEG remove shipping bolt and washer

FIGURE 7

Upflow Applications

Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al- cove installations are shown in figure 8.

Upflow Application Installation Clearances

 

Top

 

Left Side

 

Right Side

 

Bottom

 

Type of Vent

Type C

Type B1

Connector

 

 

Top

1 in. (25 mm)

1 in. (25 mm)

*Front

2−1/4 in. (57 mm)**

2−1/4 in. (57 mm)

 

 

 

Back

0

0

 

 

 

Sides

0†

0

 

 

 

Vent

6 in. (152 mm)

1 in. (25 mm)

 

 

 

Floor

0‡

0‡

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4−1/2 in. if single wall vent pipe is used.

‡For installation on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

†Left side requires 3 inches if a single wall vent is used on 14−1/2 in. cabinets, or 2inches if a single wall vent pipe is used on 17−1/2 in. cabinets.

FIGURE 8