Lennox International Inc Elite Series Gas Furnace Upflow/Horizontal Air Discharge Electrical

Models: Elite Series Gas Furnace Upflow/Horizontal Air Discharge EL280UH

1 51
Download 51 pages 39.91 Kb
Page 25
Image 25
Electrical

Leak Check

After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means.

NOTE − If emergency shutoff is necessary, shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these devices.

Manual backgroundCAUTION

Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af- ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.

The furnace must be isolated by closing its individual manual shut-off valve and disconnecting from from the gas supply system the during any pressure testing of the gas supply system at pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).

Manual backgroundIMPORTANT

When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 28. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).

MANUAL MAIN

ISOLATE

SHUT−OFF VALVE

GAS VALVE

WILL NOT HOLD

FURNACE

NORMAL TEST

 

PRESSURE

 

1/8 NPT PLUG

 

CAP

FIGURE 28

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

Manual backgroundCAUTION

Electrostatic discharge can affect elec- tronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.

The unit is equipped with a field make−up box on the left hand side of the cabinet. The make−up box may be moved to the right side of the furnace to facilitate installation. If the make−up box is moved to the right side, clip the wire ties that bundle the wires together. The excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harness to protect it from damage.

INTERIOR MAKE−UP BOX INSTALLATION

Right Side

BOX

FIGURE 29

INTERIOR MAKE−UP BOX INSTALLATION

Left side

BOX

FIGURE 30

Refer to figure 31 for schematic wiring diagram and trou- bleshooting and table 10 and figure 32 for field wiring.

The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.

NOTE − Unit nameplate states maximum current draw. Maximum over−current protection allowed is 15 AMP.

Holes are on both sides of the furnace cabinet to facilitate wiring.

Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.

Page 25

Page 25
Image 25
Lennox International Inc Elite Series Gas Furnace Upflow/Horizontal Air Discharge, EL280UH Electrical