BLOWER DATA
EL280UH110P60C PERFORMANCE (Less Filter)
|
|
|
|
| Air Volume / Watts at Different Blower Speeds |
|
|
|
| |||||||
External | Bottom Return Air, Side Return Air with Optional Return | Single Side Return Air − Air volumes in bold require field | ||||||||||||||
Static | Air Base, Return Air from Both Sides or Return Air from | fabricated transition to accommodate 20 x 25 x 1 in. air filter | ||||||||||||||
Pressure Bottom and One Side. |
|
|
|
| in order to maintain proper air velocity. |
|
|
| ||||||||
in. w.g. | High | Low | High | Low | ||||||||||||
| cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts |
0.10 | 2520 | 1359 | 2250 | 1034 | 1860 | 841 | 1455 | 654 | 2605 | 1454 | 2160 | 1060 | 1740 | 848 | 1430 | 651 |
0.20 | 2465 | 1329 | 2230 | 1018 | 1870 | 823 | 1480 | 647 | 2505 | 1401 | 2150 | 1018 | 1785 | 838 | 1450 | 649 |
0.30 | 2385 | 1307 | 2180 | 981 | 1885 | 809 | 1540 | 646 | 2435 | 1349 | 2115 | 991 | 1795 | 818 | 1485 | 638 |
0.40 | 2295 | 1256 | 2105 | 942 | 1865 | 778 | 1570 | 638 | 2350 | 1308 | 2070 | 965 | 1805 | 801 | 1480 | 631 |
0.50 | 2200 | 1214 | 2055 | 909 | 1845 | 762 | 1570 | 619 | 2260 | 1274 | 2010 | 929 | 1785 | 775 | 1480 | 621 |
0.60 | 2130 | 1186 | 1985 | 882 | 1795 | 741 | 1550 | 604 | 2175 | 1228 | 1955 | 901 | 1755 | 752 | 1490 | 611 |
0.70 | 2015 | 1150 | 1890 | 848 | 1720 | 711 | 1505 | 580 | 2085 | 1186 | 1850 | 853 | 1710 | 722 | 1460 | 594 |
0.80 | 1905 | 1105 | 1810 | 815 | 1675 | 687 | 1470 | 565 | 1965 | 1147 | 1785 | 818 | 1640 | 689 | 1425 | 567 |
NOTES - All air data is measured external to unit without filter (not furnished - field provided)
EL280UH135P60D PERFORMANCE (Less Filter)
|
|
|
|
| Air Volume / Watts at Different Blower Speeds |
|
|
|
| |||||||
External | Bottom Return Air, Side Return Air with Optional Return | Single Side Return Air − Air volumes in bold require field | ||||||||||||||
Static | Air Base, Return Air from Both Sides or Return Air from | fabricated transition to accommodate 20 x 25 x 1 in. air filter | ||||||||||||||
Pressure Bottom and One Side. |
|
|
|
| in order to maintain proper air velocity. |
|
|
| ||||||||
in. w.g. | High | Low | High | Low | ||||||||||||
| cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts | cfm | Watts |
0.10 | 2750 | 1441 | 2220 | 1056 | 1725 | 825 | 1395 | 625 | 2725 | 1463 | 2180 | 1075 | 1715 | 827 | 1320 | 624 |
0.20 | 2720 | 1392 | 2235 | 1029 | 1785 | 810 | 1445 | 618 | 2640 | 1400 | 2180 | 1051 | 1720 | 819 | 1380 | 626 |
0.30 | 2605 | 1362 | 2220 | 1002 | 1820 | 800 | 1460 | 623 | 2575 | 1374 | 2165 | 1005 | 1790 | 803 | 1420 | 622 |
0.40 | 2495 | 1312 | 2185 | 968 | 1845 | 779 | 1485 | 616 | 2495 | 1343 | 2145 | 988 | 1775 | 791 | 1450 | 617 |
0.50 | 2420 | 1275 | 2135 | 939 | 1825 | 767 | 1505 | 605 | 2405 | 1292 | 2105 | 948 | 1780 | 777 | 1470 | 610 |
0.60 | 2335 | 1234 | 2080 | 909 | 1825 | 753 | 1495 | 593 | 2305 | 1257 | 2045 | 914 | 1775 | 753 | 1480 | 593 |
0.70 | 2220 | 1190 | 1995 | 864 | 1760 | 716 | 1475 | 576 | 2215 | 1214 | 1970 | 884 | 1740 | 727 | 1455 | 583 |
0.80 | 2120 | 1157 | 1890 | 835 | 1680 | 686 | 1435 | 558 | 2110 | 1170 | 1890 | 851 | 1675 | 699 | 1430 | 565 |
NOTES - All air data is measured external to unit without filter (not furnished - field provided)
Page 38