Sequence of Operation
A Time Delay Override (TDO) button is available on the control panel to speed up the internal timer by a factor of 60 for system checkout. One second of holding down the button relates to one minute of speed up time in the control.
HEATING AND COOLING EQUIPMENT OPERATION
Heating Operation
When a zone makes a call for Heat, the W output terminal will energize. The G terminal will also energize if the ELECTRIC/GAS jumper is in the ELECT position. The W terminal
Fan Purge Time Delay
If the ELECTRIC/GAS jumper is in the ELECT position and the PURGE/NO PURGE jumper is in the PURGE position, the G terminal will remain energized for one minute after the W terminal is
If the ELECTRIC/GAS jumper is set in the GAS position, the G terminal does not turn on during purge regardless of the position of the PURGE or NO PURGE switch. Lennox furnaces will control the purge though the furnace control board cool down feature. The cool down time is often adjustable at the furnace control board up to 3.5 minutes. NO PURGE is the preferred method of purge when this zone panel is applied to Lennox equipment.
Cooling Operation
When a zone makes a call for Cooling, the Y and G terminals will energize. The Y terminal
Fan Purge Time Delay
If the PURGE/NO PURGE jumper is in the PURGE position, the G terminal will remain energized for one minute after the Y terminal is
Heat/Cool Changeover: When a call for heating or cooling exists and an opposing call is made from another zone, a 20 minute timer is activated. If the original call is not satisfied within that
High/Low Limit Temperature: The high/low limit temperature settings are designed to prevent the heat exchanger from overheating or the cooling coil from freezing. The temperature sensor in the supply duct senses the discharge air temperature and interrupts the heating/cooling equipment (depending on the Heat and Cool temperatures set on the control panel) before overheating/freezing occurs. When a heating/cooling call is interrupted by the high/low temperature limit, the zone control panel turns the equipment off and energizes the G terminal (if not already energized). The W or Y LED on the control panel will flash during a high/low limit temperature interrupt. Once the temperature drops/rises 10°F and the minimum off time has expired, the equipment is turned back on if the call for conditioning still exists. The Heating/Cooling LED will stop flashing.
IMPORTANT: Should a short or open circuit be detected across the DAS terminals, the zone system will respond only to Zone 1 and the dampers will not energize.
Page 8