ZONING SYSTEM
|
| Litho U.S.A. | |
© 2004 Lennox Industries Inc. |
|
| |
504,926M |
| ||
Dallas, Texas, USA | |||
| 5/2004 | ZONE CONTROL PANEL | |
|
|
INSTALLATION INSTRUCTIONS FOR ZONE CONTROL PANELS
USED WITH LENNOX HEATING AND COOLING EQUIPMENT
Shipping & Packing List
Package 1 of 1 contains the following:
(1)Model
(1)Model 88K38 Temperature Sensor
(1)Installation Instructions
(1)Owners Manual
(1)Warranty Card
Required Components (ordered separately):
24 VAC Transformer – The size of the transformer needed is determined by the total power requirements for the control panel, thermostats and dampers. The control panel and thermostats together require 10VA. The dampers require 10VA each. The size of the transformer will depend on the greatest number of dampers that could be energized at any given time.
NOTE – When power closed/spring open dampers are used, at least one zone’s dampers will not be energized during a call for heating or cooling.
TABLE 1 – TRANSFORMERS
Part Number | Size | Voltage Description |
|
|
|
10P17 | 40VA | |
|
|
|
10P87 | 50VA | |
|
|
|
12P61 | 75VA | |
|
|
|
83P74 |
| 4" Square Electrical Box |
|
|
|
Thermostats –
Dampers – 2 or
FIGURE 1 – LENNOX® MODEL