Sequence of Operation (continued)
CONTINUOUS FAN OPERATION
A call for Fan from any zone will initiate the G equipment output terminal. The normally open (NO) damper terminal at all zones not calling for continuous fan will be energized.
DAMPER OPERATION
The “NO” output will be energized and the “NC” output will be
Damper Purge Time Delay
When the Purge/No Purge jumper is at No Purge, the damper purge time delay is 3.5 minutes and begins when the equipment output(s) turn off. NO PURGE is the preferred method of purge control for Lennox furnaces and air conditioners. When the jumper is at Purge, the damper purge time delay is one (1) minute.