Pin Jumper Settings (see Figure 5)
FIGURE 5 – PIN JUMPER SETTINGS
ELECTRIC/GAS: If electric heat is to be used, move the jumper to the “ELECT” position. This will turn on the fan (G output terminal) with a heat call (W output terminal). If the jumper is in the “GAS” position, it is assumed that the heating equipment will control the fan operation.
NO PURGE / PURGE: If the NO PURGE / PURGE jumper is moved to the “PURGE” purge position, the G terminal will remain energized for a one minute purge delay following the completion of a cooling call. If the jumper is moved to the “NO PURGE” position, the G terminal will
DISCHARGE AIR SENSOR
IMPORTANT: The temperature sensor is required. If a short or open circuit is detected between the Discharge Air Sensor (DAS) terminals, the control panel will only respond to Zone 1 and the dampers will not close.
DISCHARGE AIR SENSOR
Jumper Settings | Mode |
| Purge |
| No Purge | |
|
|
|
|
| ||
Output | Damper Hold Time | Output |
| Damper Hold Time | ||
|
|
| ||||
|
|
|
|
|
|
|
Heat/Cool | Cooling | G1 | 1 minute | No G, |
| |
|
|
|
|
|
| |
Gas | Heating | No G | 1 minute | No G, |
| |
|
| |||||
|
|
|
|
|
|
|
Heat/Cool | Cooling | G1 | 1 minute | No G, |
| |
|
|
|
|
|
| |
Elect. | Heating | G1 | 1 minute | No G, |
| |
|
|
|
|
|
|
|
1The G terminal will remain energized for 1 minute.
LEDs
POWER – Blinks during normal operation. Starts to blink approximately 6 seconds after power up.
G, Y and W – Lights when respective equipment outputs are energized. The W LED will flash if the heating high temperature limit has been reached. The Y LED will flash if the cooling low temperature limit has been reached.
ZONE 1 Damper and ZONE 2 Damper – Lights when the Normally Open (NO) damper terminal for that zone is energized (i.e. LEDs show which zones are NOT receiving conditioning when the HVAC equipment is operating).
Page 7