| 12" (305mm) MAX. for 2" (51mm) | |
UNCONDITIONED | 20" (508mm) MAX. for 3" (76mm) | |
| ||
SPACE |
| |
6" (152mm) |
| |
Max | SIZE TER- | |
| MINATION | |
*WALL SUPPORT | PIPE PER | |
OUTSIDE WALL | TABLE 8. | |
| ||
FIELD−PROVIDED | 12" (305mm) | |
REDUCER MAY BE | ||
ABOVE GRADE OR | ||
REQUIRED TO | ||
AVERAGE SNOW | ||
ADAPT LARGER | ||
ACCUMULATION | ||
VENT PIPE SIZE TO | ||
| ||
TERMINATION |
|
1/2" (13mm) FOAM |
| |
INSULATION IN |
| |
UNCONDITIONED | 1/2" (13mm) FOAM | |
SPACE | ||
INSULATION | ||
*Use wall support every 24" (610). Use | ||
| ||
two supports if extension is greater |
| |
than 24" but less than 48". |
|
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION EX- TENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED
FIGURE 40
ML193DF NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
| SIZE TERMINATION |
|
|
| STRAIGHT−CUT OR | |||||||
| PIPE PER TABLE 8. |
|
| ANGLE−CUT IN DIRECTION | ||||||||
|
|
|
| OF ROOF SLOPE | ||||||||
|
|
|
|
|
| 3" − 8" |
|
|
|
|
| |
|
| EXHAUST VENT |
|
| ||||||||
|
|
|
|
|
| (76mm− |
|
| 1/2" (13mm) |
|
| |
|
|
|
|
|
| 203mm) |
|
|
|
| ||
|
|
|
|
|
|
|
| WEATHERPROOF |
|
| ||
Minimum 12" (305MM) |
|
|
|
| ||||||||
|
| INSULATION |
|
| ||||||||
above chimney top |
|
|
|
| ||||||||
|
|
|
|
|
| |||||||
plate or average snow |
|
|
|
|
|
| ||||||
SHOULDER OF FITTINGS |
|
| ||||||||||
accumulation |
|
| ||||||||||
| PROVIDE SUPPORT |
|
| |||||||||
|
|
|
|
|
|
| OF PIPE ON TOP PLATE |
|
| |||
|
|
| SHEET |
|
|
|
|
|
|
| ||
|
|
| METAL TOP |
|
|
|
|
|
|
| ||
|
|
| PLATE |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| 3" − 8" | ||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| (76mm− | ||||
|
|
|
|
|
|
|
| 203mm) | ||||
|
| INSULATE |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||
|
| TO FORM |
|
|
|
|
|
| EXTERIOR |
| ||
|
| SEAL |
|
|
|
|
|
| PORTION OF |
| ||
|
|
|
|
|
|
|
|
|
| CHIMNEY |
|
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver- tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus- trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 41
Condensate Piping
This unit is designed for either right- or
NOTE − If necessary the condensate trap may be installed up to 5´ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.
CONDENSATE TRAP AND PLUG LOCATIONS | ||
Trap |
| |
(same on |
| |
right side) |
| |
1−1/2 in. | Plug | |
(same on left | ||
| ||
| side) |
FIGURE 42
1 − Determine which side condensate piping will exit the unit, location of trap, field−provided fittings and length of PVC pipe required to reach available drain.
2 − Remove plug (figure 42) from the cold end header box at the appropriate location on the side of the unit. Install field−provided 1/2" NPT male fitting into cold end head- er box. Use teflon tape or appropriate pipe dope.
3 − Install the cap over the clean out opening at the base of the trap. See figure 45.
NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain on the trap using a hose clamp.
4 − Install drain trap using appropriate PVC fittings, glue all joints. Glue the provided drain trap as shown in fig- ure 45. Route the condensate line to an open drain.
NOTE − If necessary the condensate trap may be installed up to 5 feet away from the furnace. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.