FIELD SUPPLIED WALL TERMINATION OR (15F74) WALL RING TERMINATION KIT

NOTE − FIELD PROVIDED

 

 

REDUCER MAY BE

 

1/2" (13mm) ARMAFLEX

REQUIRED TO ADAPT

 

 

INSULATION IN UN-

LARGER VENT PIPE SIZE

 

 

CONDITIONED SPACE

TO TERMINATION

 

 

 

 

 

SIZE TERMINATION

 

 

PER TABLE 8

 

 

D

 

 

B

C

 

STRAIGHT

A

APPPLICATION

 

FIELD SUPPLIED WALL TERMINATION OR (15F74) WALL RING TERMINATION KIT With INTAKE ELBOW

NOTE − FIELD PROVIDED

 

REDUCER MAY BE

1/2" (13mm) ARMAFLEX

REQUIRED TO ADAPT

INSULATION IN UN-

LARGER VENT PIPE SIZE

CONDITIONED SPACE

TO TERMINATION

 

 

SIZE TERMINATION

 

PER TABLE 8

 

D

 

B

 

STRAIGHT

C

APPPLICATION

 

A

 

1/2" (13mm) ARMAFLEX INSULATION

 

IN UNCONDITIONED SPACE

 

D

* WALL

E

 

SUPPORT

 

 

B

 

A

C

EXTENDED

 

APPLICATION

* WALL

SUPPORT

C

1/2" (13mm) ARMAFLEX INSULATION

IN UNCONDITIONED SPACE

D

E

B

A

EXTENDED

APPLICATION

See venting table 7 for maximum venting lengths with this arrangement.

*Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust)

 

2" (51mm)

3" (76mm)

 

Vent Pipe

Vent Pipe

A−Minimum clearance

 

 

 

above grade or average

12" (508MM)

12" (508MM)

snow accumulation

 

 

 

 

 

 

 

B−Maximum horizontal

 

 

 

separation between

6" (152MM)

6" (152MM)

intake and exhaust

 

 

 

 

 

 

 

C−Minimum from

8" (203MM)

8" (203MM)

end of exhaust to

 

 

 

inlet of intake

 

 

 

D−Maximum exhaust

12" (305MM)

20" (508MM)

pipe length

 

 

 

 

 

 

 

E−Maximum wall support

 

 

 

distance from top of each

6" (152MM)

6" (152MM)

pipe (intake/exhaust)

 

 

 

 

 

 

 

FIGURE 28

See venting table 7 for maximum venting lengths with this arrangement.

*Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust)

 

2" (51mm)

3" (76mm)

 

Vent Pipe

Vent Pipe

 

A−Minimum clearance

12" (508MM)

12" (508MM)

above grade or average

snow accumulation

 

 

 

B−Maximum horizontal

6" (152MM)

6" (152MM)

separation between

 

 

 

intake and exhaust

 

 

 

C−Minimum from

 

 

 

end of exhaust to

6" (152MM)

6" (152MM)

inlet of intake

 

 

 

D−Maximum exhaust

12" (305MM)

20" (508MM)

pipe length

 

 

 

 

 

 

 

E−Maximum wall support

 

 

 

distance from top of each

6" (152MM)

6" (152MM)

pipe (intake/exhaust)

 

 

 

 

 

 

 

FIGURE 29

Page 23

Page 23
Image 23
Lennox International Inc MERIT SERIES GAS FURNACE DOWNFLOW AIR DISCHARGE Reducer MAY be, Required to Adapt, Support