Lennox International Inc ML193DF Gas Pressure Adjustment, Proper Combustion

Models: MERIT SERIES GAS FURNACE DOWNFLOW AIR DISCHARGE ML193DF

1 52
Download 52 pages 25.88 Kb
Page 38
Image 38
Gas Pressure Adjustment

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 11

GAS METER CLOCKING CHART

 

Seconds for One Revolution

 

 

 

 

 

 

 

ML193

Natural

 

LP

 

Unit

1 cu ft

2 cu ft

 

1 cu ft

 

2 cu ft

 

Dial

Dial

 

Dial

 

DIAL

 

 

 

 

 

 

 

−045

80

160

 

200

 

400

 

 

 

 

 

 

 

−070

55

110

 

136

 

272

 

 

 

 

 

 

 

−090

41

82

 

102

 

204

 

 

 

 

 

 

 

−110

33

66

 

82

 

164

 

 

 

 

 

 

 

Natural−1000 btu/cu ft

LP−2500 btu/cu ft

 

NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.

Furnace should operate at least 5 minutes before check- ing gas flow. Determine time in seconds for two revolu- tions of gas through the meter. (Two revolutions assures a more accurate time). Divide by two and compare to time in table 11. If manifold pressure matches table 12 and rate is incorrect, check gas orifices for proper size and restric- tion. Remove temporary gas meter if installed.

Supply Pressure Measurement

A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. See table 12 for proper supply line pressure. Replace the threaded plug af- ter measurements have been taken.

TABLE 12

Manifold and Supply Pressure (Outlet) inches w.c.

 

Model

 

Supply

 

Manifold

Pressure in.wg.

Fuel

Input Sizes

Pressure in.wg.

 

 

 

 

Min.

Max.

 

 

 

 

 

 

 

 

Nat. Gas

All sizes

3.5

4.5

10.0

 

 

 

 

 

 

 

L.P. Gas

All sizes

10.0

11.0

13.0

 

 

 

 

 

 

 

NOTE − A natural to L.P. propane gas changeover kit is nec- essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Manifold Pressure Measurement

1 − Remove the threaded plug from the outlet side of the gas valve and install a field−provided barbed fitting. Connect to a manometer to measure manifold pres- sure.

2 − Start unit and allow 5 minutes for unit to reach steady state.

3 − While waiting for the unit to stabilize, notice the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.

4 − After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table 12.

NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.

Proper Combustion

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com- bustion. Take combustion sample beyond the flue outlet and compare to the tables below. The maximum carbon monoxide reading should not exceed 50 ppm.

TABLE 13

ML193

CO2% For Nat

CO2% For L.P.

Unit

 

 

 

 

 

−045

 

 

 

 

 

−070

7.2 − 7.9

8.6 − 9.3

 

−090

 

 

 

 

 

−110

 

 

 

 

High Altitude Information

 

 

 

 

NOTE − In Canada, certification for installations at eleva- tions over 4500 feet (1372 m) is the jurisdiction of local au- thorities.

ML193DF units require no manifold pressure adjustments for operation at altitudes up to 10,000 feet (3048 m) above sea level. Units installed at altitude of 4501 − 10,000 feet (1373 to 3048m) require a pressure switch change which can be ordered separately. Table 14 lists conversion kit and pressure switch requirements at varying altitudes.

The combustion air pressure switch is factory−set and re- quires no adjustment.

NOTE − A natural to LP/propane gas changeover kit is nec- essary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

Page 38

Page 38
Image 38
Lennox International Inc ML193DF Gas Pressure Adjustment, Proper Combustion, High Altitude Information