![TROUBLESHOOTING](/images/new-backgrounds/35429/3542923x1.webp)
12
TROUBLESHOOTING
Note: Before troubleshooting the gas control system, Ensure external gas shut off valve, located at gas supply inlet, (and wall switch, iff applicable), is
in the “ON” position. Important: Valve system troubleshooting should only be accomplished by a qualified service technician.
TROUBLESHOOTING GUIDE - MILLIVOLT GAS CONTROL SYSTEM
| SYMPTOM | POSSIBLE CAUSES | CORRECTIVE ACTION |
1. | Spark igniter will not light pilot after | A. Defective igniter | Check for spark at electrode and pilot; if no spark and |
| repeated triggering of igniter button. | (no spark at electrode). | electrode wire is properly connected, replace igniter. |
|
| B. Defective or misaligned electrode at pilot | Using a match, light pilot. If pilot lights, turn off pilot |
|
| (spark at electrode). | and trigger the igniter button again. If pilot lights, an |
|
|
| improper gas mixture caused the bad lighting and |
|
|
| a longer purge period is recommended. If pilot will |
|
|
| not light – check gap at electrode and pilot – should |
|
|
| be 1/8" to have a strong spark. If gap measures 1/8", |
|
|
| replace pilot (see Figure 17 on Page 14). |
|
| C. Gas supply pressure errant. | Check inlet gas pressure. It should be within the limits |
|
|
| as marked on the rating plate. |
|
| D. Pilot orifice plugged. | Clean or replace pilot orifice. |
2. | Pilot will not stay lit after | A. Defective pilot generator | Check pilot flame, it must impinge on thermocouple |
| carefully following the lighting | (thermocouple). | (see Figure 17 on Page 14). Clean and/or adjust pilot |
| instructions. |
| for maximum flame impingement on thermocouple. |
|
|
| Ensure that the connection between the valve and |
|
|
| thermocouple are tight and secure. |
3. | Pilot burning, no gas to burner, Valve | A. Manual Reset Spill Switch has Tripped or is | Follow Manual Reset procedure on Page 6. Once the |
| knob “ON,” and the (standard) burner | defective. | red reset button is fully depressed and clicks in, check |
| OFF/ON switch is “ON." Read impor- |
| continuity with a multimeter between switch terminal |
| tant note below. |
| |
|
| (Ohms). If it shows an open circuit, replace switch. | |
|
|
| |
|
|
|
|
| IMPORTANT NOTE: If an optional | B. Wall switch or wires defective. | Check wall switch and wires for proper connections. |
|
| Jumper wire across terminals at wall switch, if burner | |
| *remote switch is used for burner |
| comes on, replace defective wall switch. If okay, jumper |
| operation, the standard burner |
| wires across wall switch wires at valve, if burner comes |
| OFF/ON switch on appliance must |
| on, wires are faulty or connections are bad. |
| be in the "OFF" position. |
|
|
| C. Thermopile may not be generating suf- | Check thermopile with millivolt meter. Take reading | |
|
| ||
| *Optional remote switch kits - wall | ficient millivolts. | at thermopile terminals of gas valve. Should read |
| switch or remote control. |
| 325 millivolts minimum with optional wall switch |
|
|
| “OFF.” Replace faulty thermopile if reading is below |
|
|
| specified minimum. |
|
| D. Plugged burner orifice. | Check burner orifice for blockage and remove. |
|
|
|
|
|
| E. OFF/ON Switch & *Remote Switch are in | When turning on the burner using a *remote switch, |
|
| the "ON" position resulting in excessive | ensure that the standard OFF/ON switch is in the "OFF" |
|
| resistance. | position. If both switches are in the ON position, it |
|
|
| may result in excessive resistance (& millivolt drain- |
|
|
| age) and the burner may not come on. |
4. | Frequent pilot/burner outage prob- | A. Pilot flame may be too low or blowing (high) | Clean and/or adjust pilot flame for maximum flame |
| lem. | causing the pilot/valve safety to drop out. | impingement on thermocouple (see Figure 19 on |
|
|
| Page 20). |
TROUBLESHOOTING GUIDE - ELECTRONIC IGNITION SYSTEM
| SYMPTOM |
| POSSIBLE CAUSES | CORRECTIVE ACTION |
|
|
|
| |
1. | Burner will not light. | A. Faulty Valve System. | See Below. | |
|
|
|
| |
|
| B. “OFF/ON” or wall switch defective. | Disconnect the two black wires from the wire nuts. | |
|
|
|
| Test switch(s) for continuity with a multimeter. If |
|
|
|
| continuity is not indicated, switch(s) is defective and |
|
|
|
| must be replaced. |
|
|
|
| Note: Before replacing “OFF/ON” switch, Ensure to |
|
|
|
| check wiring for loose connections or broken wires |
|
|
|
| and repair as needed. |
|
|
|
| |
2. | Burners come “ON,” then turns “OFF.” | A. Burner orifice plugged. | Check main burner orifice(s) for blockage. Clean | |
|
|
|
| or replace. |
|
|
|
| |
|
| B. Obstructed vent system. | Check vent system for obstructions. | |
|
|
| NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. |
|
|
|
|
|