CAUTION

After the confirmation of the above conditions, prepare the wiring as follows:

1)Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.

2)Provide a circuit breaker switch between power source and the unit.

3)The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)

4)Specification of power source

5)Confirm that electrical capacity is sufficient.

6)Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.

7)Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)

8)Never fail to equip a leakage breaker where it is wet or moist.

9)The following troubles would be caused by voltage drop-down.

Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.

Proper starting power is not given to the compressor.

HAND OVER

Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

If Error Code happens in the display of indoor.

 

Error Code

Error Contents

 

Checking Point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Air Sensor Open or Short

 

C0

 

 

 

 

 

1.Check Sensor Connection to PCB whether it's

 

 

 

 

 

 

connected well or not.

 

 

 

 

 

 

 

 

 

 

 

 

 

2.Replace it with new Sensor.

 

 

 

C1

Indoor Pipe Sensor Open or Short

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Sensor Open or Short

 

 

 

 

 

 

C3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C4

Outdoor Pipe Sensor Open or Short

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C5

Communication failure between

 

 

 

 

 

1.Check connecting cable wiring order between

 

 

 

Indoor and outdoor unit.

 

 

Indoor and outdoor diagram.

 

 

 

 

 

 

 

2.Check all wire connector whether it is connected

 

 

 

 

 

 

 

or not.

 

 

 

 

 

 

 

 

 

 

 

 

3.Indoor AC PCB defects.(short inside).

 

 

 

 

 

 

 

4.Outdoor PCB defects.(short inside)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

–26–

Page 26
Image 26
LG Electronics LF300CP(LP-C303R20), LF480CE(LP-C483TA0) service manual Hand Over