WHAT TROUBLED

 

COMPLAINTS

 

HOW TO CHECK

 

REMEDY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric troubles

Defective contact.

Checking

Repair and clean or

 

(Magnetic

 

 

Defective contact point.

 

 

 

 

 

replace it.

 

 

contactor)

 

 

Rusting and faults in the iron

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

core contact face. Defective

 

 

 

 

 

 

 

 

 

 

 

contact of the

 

 

 

 

 

 

 

 

 

 

 

operating switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Others

 

Improper installation

 

 

 

 

 

 

 

 

 

 

 

 

Correct it.

 

 

 

Checking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trouble checking by protection devices

 

 

 

 

 

 

 

Fault

 

 

 

Cause

 

 

Check/Correcitve Action

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Discharge

 

 

 

 

Condenser cooling air extremely hot or

 

 

1. Check the operation of the outdoor motor.

 

 

 

 

 

 

 

 

insufficient air flow through the condenser

 

 

2. Check discharge and suction, air

 

 

 

 

 

 

 

 

 

circulation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inside of the condenser tube is clogged.

 

 

Clean condenser coil.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Purge air from the cycle.

 

 

 

 

 

 

 

 

Air in the refrigeration cooling cycle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction pressure is higher than standard.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See "High Suction Pressure".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Check unit operation input

 

Low

 

 

 

 

 

Faulty discharge valves or suction valves of

 

Discharge

 

 

 

 

 

the compressor.

 

 

2. Check the suction pressure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant low-charge or leakage.

 

 

 

 

 

 

 

 

 

 

Add refrigerant: repair leakage if any.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction pressure is lower than standard.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See "Low Suction Pressure".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Check fresh air, intake or check for

 

 

 

 

 

 

Intake air extemely hot or excessive air flow

 

High

 

Suction

 

 

 

through the evaporator coil.

 

 

 

leakage of the return air.

 

Pressure

 

 

 

 

 

 

 

 

 

2. Check air flow quantity.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant over-charge.

 

 

Purge the refrigerant.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Faulty discharge valve or suction valve of

 

 

Check the operating input.

 

 

 

 

 

 

 

 

the compressor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge pressure is higher than standard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See "High discharge Pressure".

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Intake air extremely cold or insufficient air

 

 

1. Check air flow quantity.

 

Low

 

Suction

 

 

 

flow through the evaporator coil.

 

 

2. Check air filter.

 

 

Pressure

 

 

 

 

 

 

 

3. Check evaporator coil frosting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Add refrigerant, repair leakage, if any.

 

 

 

 

 

 

 

 

Refrigerant short-charge or leakage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Restricted liquid in the suction line.

 

Check the capillary tube and the strainer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 