Fault | Cause | Check/Correcitve Action | |
|
|
| |
| Discharge pressure is lower than standard. | See "Low Discharge Pressure". | |
|
|
| |
| Single or three phases running. | Check the power supply line and the | |
|
| contactor. | |
|
|
| |
| High or low voltage or phase unbalance. | Check the voltage and phase unbalance. | |
|
|
| |
Internal | Refrigerant short charge or leakage. | Add refrigerant, repair leakage, if any. | |
Thermostat |
|
| |
|
| ||
Compressor frequently stops and starts. | Check thermistor operation, or any other | ||
| |||
|
| cause for frequent stop and start operation. | |
|
|
| |
| Discharge and suction pressure are | See "High Discharge Pressure" or "High | |
| extremely high. | Suction Pressure". | |
|
|
| |
Overcurrent | High or low voltage, or phase unbalance. | Check the voltage and phase unbalance. | |
|
| ||
Relay for | Single or three phases running | Check the power supply line and the | |
Compressor | |||
| contact. | ||
| |||
|
| ||
Faulty compressor motor. | Check electric resistance among the | ||
| |||
|
| compressor terminals, and from the | |
|
| terminals to ground. | |
|
|
| |
| Loose connections. | Check the electric connections. | |
|
|
| |
| Compressor frequently stops and starts. | Check the operation of the thermistor, or | |
|
| any other cause for frequent stop. | |
|
|
| |
Overcurrent | High or low voltage, or phase unbalance. | Check the voltage and electric wiring. | |
|
| ||
Relay for | Single or three phases running. | Check the power supply line and the | |
Fan Motor |
| contactor. | |
|
| ||
Faulty fan motor. | Check the fan motor and wiring. | ||
| |||
|
|
| |
| Loose connection. | Check the elelctric connections. | |
|
|
| |
| Faulty fan bearing. | Check repair or replace the bearing. | |
|
|
| |
| Loose connections. | Check the electric connections. | |
Fuse Blown |
|
| |
Single or three phase running. | Check the power supply line. | ||
| |||
|
|
| |
| Faulty motor. | Check electric resistance among motor | |
|
| housing, and from the terminals to | |
|
| ground. | |
|
|
| |
Disconnection | Disconnection. | 1. Check the wires and connect where | |
and Faulty |
| necessary. | |
| 2. Check the contact holding coil. | ||
Contact |
| ||
|
| ||
|
|
| |
| Faulty contact. | Check the contact in the magnetic | |
|
| contact, the | |
|
| pressure control switch, the operation | |
|
| switch, the auxiliary relay. | |
|
|
|