7) No heating operation works
NO
ON/OFF S/W ON
Is the AC220V
(AC 240 V) between connector
NO
Is the unit operating?
YES
Is it heating mode?
YES
Is the input power AC220V (AC240V) at COMP magnetic coil contactor?
YES
Check the COMP magnetic contactor of outdoor unit.
NO
NO
Check the wiring
connection
YES
Room temp <Set temp?
YES
Is the DC5V
at 14 pin of Micom terminal
YES
Is the DC5V
at 18 pin of Micom terminal
YES
Is the DC12V
at each terminal?
YES
Is the
AC220V (AC 240 V) between connector(4WAY) and
P.C.B
YES
Is the DC12V at each terminal?
YES
Is the AC220V
(AC 240 V) between
Pin 1 and Pin 3 of Main
P.C.B
Select the heating operation mode.
NO
Room temp. < Set temp. Setting
NO
Replacement MICOM
NO
Replacement MICOM
NO | Replacement ICO2M |
|
NO
Replacement
NO | Replacement ICO2M |
|
NO
Replacement
YES