3) Only outdoor fan does not work

 

 

 

 

 

 

 

WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

Over-heated

Check how it is insulated.

Repair or replace it.

 

 

Layer short

 

 

 

 

 

 

 

 

 

Electric Wiring

Open wire on operation

Check it with a tester.

Rewiring or repair.

 

 

 

 

 

 

 

 

Short circuited on

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

4) Only compressor does not work

 

 

 

 

 

 

 

WHAT TROUBLED

COMPLAINTS

HOW TO CHECK

REMEDY

 

 

 

 

 

 

 

Magnetic switch for

Defective contact,

Check it with the eyes on

Repair or replace it.

 

compressor motor

magnetic coil troubled.

with a tester.

 

 

 

 

 

 

 

 

Compressor motor

Troubled over-heated

Check how it is insulated.

Replace or repair the

 

 

(layer short)

 

compressor.

 

 

 

 

 

 

Compressor

Troubled or over-heated

Groaned noise of motor

Repair or replace it.

 

 

(lock)

 

 

 

 

 

 

 

 

 

High pressure switch

Troubled or defective

Check it with a tester.

Replace it if necessary.

 

 

contact or operating

 

 

 

 

 

 

 

 

 

Electric circuit

Defective connection or

Check it with a tester.

Rewiring or push reset

 

 

disconnection of the circuit

 

button.

 

 

for compressor.

 

 

 

 

 

 

 

 

 