Response to Abnormal Conditions
IEEE 1547 (Default)
Parameter | Range | Clearing Time (s) | |
Phase Voltage | V < 60V | <0.16 | |
|
|
| |
| 60V ≤ V < 106V | < 2.00 | |
|
|
| |
Voltage | 132 ≤ V < 144V | < 1.00 | |
|
|
| |
| V ≥ 144V | < 0.16 (< 0.016, Hawaii mode - TOV)1) | |
Frequency | > 60.5Hz | < 0.16 | |
|
| ||
< 59.3Hz (< 57 Hz, Hawaii mode)1) | < 0.16 | ||
|
Note 1 : This test is performed in nominal conditions, except for test parameter
Note 2 : After clearing, if grid returns to the normal state, it takes up to 5 minutes for operation of AC module
Dedicated Cables
| Trunk |
|
Type |
| |
Max. Voltage |
| 600V |
Cable |
| 20A |
Max. Current |
| |
Size |
| 12AWG |
Max. Voltage |
| 300V |
Connector |
| 20A |
Max. Current |
| |
| Drop |
|
Type |
| |
Max. Voltage |
| 600V |
Cable |
| 5A |
Max. Current |
| |
Size |
| 18AWG |
Max. Voltage |
| 300V |
Connector |
| 5A |
Max. Current |
| |
| Certification |
|
UL9703, UL6703A |
| |
| Dimensions |
|
400 mm |
| |
(95.75 inch) |
| |
53 mm | 31.5 mm |
|
(2.09 inch) | (1.24 inch) |
|
122 mm |
|
|
(4.80 inch) | 1,200 mm | 66 mm |
| (47.24 inch) | (2.60 inch) |
4 |
|
|