Ex) Web Event Screen
1Current Issues : Provides the current conditions of the system.
2Event History : Provides the event records for aspecified period.
3Click the device in the query results to check the “Issue Details”. A 
Affected devices, alert type, alert duration and detailed descriptions.
Notice #1 and #2 AC Voltage High/ Low
•It occurs when the system voltage is lower or higher than the operational threshold. Due to a problem of the power company, it can temporarily happen or and it is automatically adjusted by the power company. If the problem persists, check the followings.
| Nominal Voltage 240 Volt AC | Nominal Voltage 208 Volt AC | ||
| L1, L2 to neutral | 106 to 132 Vac | L1, L2, L3 to neutral | 106 to 132 Vac | 
| L1 to L2 | 211 to 264 Vac | L1 to L2 to L3 | 183 to 229 Vac | 
Ex) Voltage Low Screen
| App Message Screen | Web Event Screen | 
•Check the voltage at terminals in the distribution 
9