Table 3

UPS Module Power Wiring Termination - Factory Supplied

 

 

 

 

 

 

 

Connection Type / Wire Size Range

 

 

 

UPS Module

 

 

 

 

 

Rating

 

AC Input

Battery

AC Output

Neutral

Ground

kVA

 

12 - 24

 

Compression

Studs

Compression

Compression

Copper Busbar

 

 

lug

3/8 - 16 x 2

lug

lug

3.75 x 3.75 x

 

 

#14 to #2/0

Lugs Required

#14 to #2/0

#14 to #2/0

0.25

 

 

 

 

 

 

 

Use factory supplied connections for terminations where they are provided. Refer to Figure 19 for field- supplied wiring termination details. Use commercially available UL listed solderless lugs for the wire size required for your application. Connect wire to the lug using tool and procedure specified by the lug manufacturer.

Table 4

Torque Specifications (Unless Otherwise Labeled)

 

 

 

 

 

 

 

 

 

Nut and Bolt Combinations

 

 

 

 

 

 

 

 

 

Grade 2

Electrical Connections

 

Bolt Shaft Size

 

 

Standard

with Belleville Washers

 

 

 

 

 

 

 

 

Inches

 

Lb-in

 

N-m

Lb-in

N-m

 

1/4

 

70

 

8.0

46

5.2

 

 

 

 

 

 

 

 

 

5/16

 

132

 

15

60

6.8

 

 

 

 

 

 

 

 

 

3/8

 

229

 

26

95

10.7

 

 

 

 

 

 

 

 

 

1/2

 

476

 

54

256

28.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Block Compression Lugs

 

 

 

 

 

 

UPS Module

 

 

 

Wire Size or

 

 

 

Rating

 

Wiring

 

Lb-in

N-m

 

kVA

 

 

Range

 

12 - 24

 

Control

 

#22 - #14

3.5 to 5.3

0.4 to 0.6

 

 

 

 

 

 

 

 

 

12 - 24

 

Power

 

#6 - 350 MCM

50

5.6

 

 

 

 

 

 

 

 

16 Installation

Page 22
Image 22
Liebert 50 and 60 Hz, S3 user manual 10.7, 28.9, #6 350 MCM