Table 5

Alarm Messages (continued)

 

 

 

 

Alarm Message

Meaning

Corrective Action

 

 

 

LAN Interface Shutdown

This alarm indicates the LAN is being

This should activate the automatic

Initiated

 

shut down for a programmed action

shutdown sequence programmed

 

 

due to the activation of one or more

into your LAN operating system.

 

 

alarms.

 

 

 

 

Load on Manual Bypass

The Maintenance Bypass switch is in

When the maintenance activity has

 

 

the Maintenance position.

been completed, return the unit to

 

 

 

normal operation.

 

 

 

 

Logic Error

 

Automatic diagnostic testing has

Record the alarm condition and

 

 

detected a failure (of hardware or

contact Liebert Global Services.

 

 

software) in the UPS internal control

 

 

 

system. A second message may

 

 

 

indicate internal test or software

 

 

 

time-out. The load has been

 

 

 

automatically transferred to bypass.

 

 

 

 

Low Battery Shutdown

Battery has discharged to the

When the battery has recharged and

 

 

minimum allowable voltage. If the

if there is not fault, the unit will

 

 

bypass is available the unit will

retransfer from bypass. If bypass

 

 

transfer to bypass. If the bypass is

was not available, when input power

 

 

not available, the UPS is shut down.

becomes available, perform a UPS

 

 

No power is being supplied to the

start-up procedure. Unit will start-up

 

 

critical load.

by itself if auto-restart is enabled.

 

 

 

Low Battery Warning Issued

The battery voltage measurement

User should take appropriate

 

 

has reached the user-programmed

measures to insure an orderly

 

 

warning value. The unit will shut

shutdown of the system. If the user

 

 

down at the specified time if input

has set the warning level above 2

 

 

power is not restored.

minutes, you may also take action to

 

 

 

shed load and increase battery time

 

 

 

to complete discharge.

 

 

 

Manual Off Activated

The UPS has been shut down

To restart the UPS follow the

(Alarm History Only)

remotely through the RS-232

procedures in 3.0 - Operation.

 

 

interface or through the advanced

 

 

 

configuration menu.

 

 

 

 

Manual On Activated

The UPS has been turned on

This is an information alarm only.

(Alarm History Only)

remotely through the RS-232

Make sure it is OK that the UPS is

 

 

interface or through the advanced

energized.

 

 

configuration menu.

 

 

 

 

Manual Transfer-to-Bypass

The UPS has been transferred to

Determine why the UPS was

Activated

 

bypass remotely through the RS-232

transferred to bypass. Clear the fault

(Alarm History only)

interface or through the advanced

or problem and retransfer to normal

 

 

configuration menu. The UPS stays

operation. If the problem cannot be

 

 

on Bypass until the retransfer is

corrected, contact Liebert Global

 

 

activated and all required conditions

Services.

 

 

for retransfer are satisfied.

 

 

 

 

Memory Failure ROM or

The microprocessor has failed a self

Contact Liebert Global Services.

Memory Failure RAM

diagnostic test during the start-up

 

 

 

process. Start up will not be allowed.

 

 

 

 

Neutral SCR Short

On units equipped with the isolated

Contact Liebert Global Services.

 

 

neutral option, the SCR that transfers

 

 

 

the neutral has failed short.

 

 

 

 

Non Volatile Ram U88

Non Volatile ram has a long life

Contact Liebert Global Services.

Corrupted

 

(10 year) back up battery, either the

 

 

 

battery is near end or life or the

 

 

 

memory has been corrupted.

 

 

 

 

Non Volatile Ram U88 Failed

Non Volatile ram back up battery has

Contact Liebert Global Services.

 

 

reached end of life or the Main

 

 

 

control board memory has had a

 

 

 

failure.

 

 

 

 

 

54 Operation

Page 60
Image 60
Liebert 50 and 60 Hz, S3 user manual Procedures in 3.0 Operation