Table 5

Alarm Messages (continued)

 

 

 

 

Alarm Message

Meaning

Corrective Action

 

 

 

Output Overload

The units total output power (the sum

Determine cause of the overload and

 

 

of all three phases) has exceeded

reduce the load.

 

 

the overload capacity of the unit. The

 

 

 

load will be automatically transferred

 

 

 

to bypass (if available).

 

 

 

 

Output Undervoltage

UPS output voltage or current is not

Contact Liebert Global Services if the

Output Overvoltage

within the acceptable range. The

UPS is not able to correct any one of

Overload Phase A

load has been automatically

these conditions.

Overload Phase B

transferred to bypass (if available).

 

Overload Phase C

An automatic retransfer will be

 

 

 

attempted when the output voltage

 

 

 

and current are within tolerance.

 

 

 

 

PFC Bus Voltage High

The inverter bus voltage is either

Contact Liebert Global Services.

PFC Bus Voltage Low

high or low or exceeded acceptable

 

PFC Hardware Shutdown

limits. The unit will transfer to bypass.

 

 

 

 

Site Wiring Error

Warning Alarm: The power

Disconnect power from the UPS

 

 

conductors are not wired to the UPS

input and correct the wiring. Wiring

 

 

input in the desired sequence.

should be verified or corrected by a

 

 

 

qualified electrician.

 

 

 

System shutdown impending

The input filter may be clogged or 1

Check input air filter. Reduce the

due to over-temperature

or more cooling fans may have failed

system load as much as possible.

 

 

and the internal temperatures are

Contact Liebert Global Services.

 

 

approaching the automatic shutdown

 

 

 

level.

 

 

 

 

System shutdown due to

The UPS system has shut down and

Contact Liebert Global Services.

internal over-temperature

transferred to Bypass as a result of a

 

 

 

clogged input filter or failure of 1 or

 

 

 

more fans.

 

 

 

 

Temporary Overload

The output waveform is distorted. If

Normally the condition will correct

 

 

available, the UPS will transfer to

itself. If the unit has not corrected this

 

 

bypass until the waveform distortion

condition within 30 minutes, contact

 

 

is corrected.

Liebert Global Services.

 

 

 

UPS Overtemp

System shutdown impending due to

An over-temperature condition is

 

 

over-temperature.

present in the UPS cabinet. The UPS

 

 

This is a two-stage alarm. The same

will automatically transfer to bypass if

 

 

message will occur if the system has

the over-temperature continues.

 

 

reached over-temp and has

Determine the cause of the condition

 

 

transferred to bypass as a result of

and correct it if possible. Check for

 

 

the over-temp condition.

restricted air flow or fan failure.

 

 

Other alarms will signal the transfer

 

 

 

to bypass.

 

 

 

 

UPS Shutdown

The UPS has detected a fault and

Review and record alarm messages.

 

 

has shut down, resulting in loss of

Contact Liebert Global Services.

 

 

power to the critical load.

 

 

 

 

 

Liebert Global Services 1-800-543-2378