Table 5 | Alarm Messages (continued) |
| |
|
|
| |
Alarm Message | Meaning | Corrective Action | |
|
|
| |
Output Overload | The units total output power (the sum | Determine cause of the overload and | |
|
| of all three phases) has exceeded | reduce the load. |
|
| the overload capacity of the unit. The |
|
|
| load will be automatically transferred |
|
|
| to bypass (if available). |
|
|
|
| |
Output Undervoltage | UPS output voltage or current is not | Contact Liebert Global Services if the | |
Output Overvoltage | within the acceptable range. The | UPS is not able to correct any one of | |
Overload Phase A | load has been automatically | these conditions. | |
Overload Phase B | transferred to bypass (if available). |
| |
Overload Phase C | An automatic retransfer will be |
| |
|
| attempted when the output voltage |
|
|
| and current are within tolerance. |
|
|
|
| |
PFC Bus Voltage High | The inverter bus voltage is either | Contact Liebert Global Services. | |
PFC Bus Voltage Low | high or low or exceeded acceptable |
| |
PFC Hardware Shutdown | limits. The unit will transfer to bypass. |
| |
|
|
| |
Site Wiring Error | Warning Alarm: The power | Disconnect power from the UPS | |
|
| conductors are not wired to the UPS | input and correct the wiring. Wiring |
|
| input in the desired sequence. | should be verified or corrected by a |
|
|
| qualified electrician. |
|
|
| |
System shutdown impending | The input filter may be clogged or 1 | Check input air filter. Reduce the | |
due to | or more cooling fans may have failed | system load as much as possible. | |
|
| and the internal temperatures are | Contact Liebert Global Services. |
|
| approaching the automatic shutdown |
|
|
| level. |
|
|
|
| |
System shutdown due to | The UPS system has shut down and | Contact Liebert Global Services. | |
internal | transferred to Bypass as a result of a |
| |
|
| clogged input filter or failure of 1 or |
|
|
| more fans. |
|
|
|
| |
Temporary Overload | The output waveform is distorted. If | Normally the condition will correct | |
|
| available, the UPS will transfer to | itself. If the unit has not corrected this |
|
| bypass until the waveform distortion | condition within 30 minutes, contact |
|
| is corrected. | Liebert Global Services. |
|
|
| |
UPS Overtemp | System shutdown impending due to | An | |
|
| present in the UPS cabinet. The UPS | |
|
| This is a | will automatically transfer to bypass if |
|
| message will occur if the system has | the |
|
| reached | Determine the cause of the condition |
|
| transferred to bypass as a result of | and correct it if possible. Check for |
|
| the | restricted air flow or fan failure. |
|
| Other alarms will signal the transfer |
|
|
| to bypass. |
|
|
|
| |
UPS Shutdown | The UPS has detected a fault and | Review and record alarm messages. | |
|
| has shut down, resulting in loss of | Contact Liebert Global Services. |
|
| power to the critical load. |
|
|
|
|
|
Liebert Global Services 1-800-543-2378