Table 5

Alarm Messages

 

 

 

 

 

 

Alarm Message

 

Meaning

Corrective Action

 

 

 

 

Alarm Event

 

The Input contact isolator allows the

Scroll through the alarm messages to

 

 

 

user to define events outside of the

determine which outside alarm has

 

 

 

UPS that will cause an alarm to show

occurred. Correct the alarm source

 

 

 

on the UPS. One of those events has

and the alarm message will clear.

 

 

 

occurred.

 

 

 

 

 

Bad Connection

 

An internal connection between PC

Contact Liebert Global Services.

 

 

 

boards has come loose or is broken.

 

 

 

 

 

Battery Charger Inhibited:

 

The input contact isolator option has

This alarm normally comes when the

load above threshold

 

triggered inhibition of the battery

unit is being fed by an alternate

 

 

 

charger and the load is above the

source such as a generator. Battery

 

 

 

threshold selected by the user to

charging has been temporarily

 

 

 

inhibit battery charging.

inhibited to reduce the load on the

 

 

 

 

secondary source. If the normal utility

 

 

 

 

is supplying the load check the

 

 

 

 

programming of the ICI option in the

 

 

 

 

User’s Option Manual. If the unit is

 

 

 

 

being temporarily supplied by a

 

 

 

 

secondary source, try to reduce the

 

 

 

 

load below that sources capacity so

 

 

 

 

the system can resume charging.

 

 

 

 

Contact Liebert Global Services if

 

 

 

 

you have questions or problems.

 

 

 

 

Battery Test Failed

 

The battery test has detected a weak

If there is no charger alarm, then the

 

 

 

battery.

battery has either weak cells or loose

 

 

 

 

connections. Contact Liebert Global

 

 

 

 

Services for battery service.

 

 

 

 

Battery Voltage Unstable

 

A battery cell(s) is not functioning

Contact Liebert Global Services for

 

 

 

properly or battery system wiring is

battery service.

 

 

 

loose.

 

 

 

 

 

Bypass Out-of-Sync

 

Bypass input is not stable. UPS

If the problem does not correct itself

 

 

 

inverter output is not synchronized

in 15 minutes contact Liebert Global

 

 

 

with the input power. Automatic

Services. Check utility source.

 

 

 

transfers to bypass are prohibited.

 

 

 

 

This is usually a temporary condition.

 

 

 

 

 

Bypass Overload

 

An overload condition has exceeded

Correct the overload condition. Call

 

 

 

the capacity of the bypass. If not

Liebert Global Services if the

 

 

 

corrected a fuse will blow resulting in

condition persists.

 

 

 

a system shutdown.

 

 

 

 

 

Bypass Power Supply Failure

 

Control power is outside the

Contact Liebert Global Services.

 

 

 

acceptable limits. Bypass is not

 

 

 

 

available.

 

 

 

 

 

Bypass SCR Short

 

The system has sensed unexpected

Contact Liebert Global Services.

 

 

 

input voltage. The UPS will transfer

 

 

 

 

to bypass.

 

 

 

 

 

Bypass Sensing Failure

 

Unit will transfer to bypass due to an

Contact Liebert Global Services.

 

 

 

internal sensing failure.

 

 

 

 

 

Bypass Voltage

 

Input power voltage or frequency is

In this condition a manual transfer to

Out of Tolerance

 

outside of the specified tolerance.

bypass is not recommended because

Incorrect Bypass

 

Automatic transfers to bypass are

it will be a momentarily interrupted

 

prohibited except in the case of

transfer.

Input Frequency

 

inverter failure.

 

 

 

 

 

Can’t Execute Battery Test:

 

The battery has discharged too

No corrective action is required. The

Not Recharged

 

recently (within 72 hours of the

next scheduled battery test will be

 

 

 

scheduled test time).

performed.

 

 

 

 

 