Installation
8.Secure front of the equipment to rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on front of the equipment that align with the center holes on return flange of front members, you can use the four (4) extra M5 screws provided in this kit to secure the equipment. Otherwise, the equipment should be secured to front of rack mounting rails with four (4)
9.To orient the display for horizontal viewing, remove the front plastic bezel by pulling forward evenly on both sides. The unit has two front panel overlays. Remove the outer overlay (used for tower installation). This reveals a horizontally oriented front panel overlay for rack mounting. Snap the front bezel back into place.
10.Once the UPS is installed in the rack, the load may be connected. Ensure the load equipment is turned off; plug all loads into the output receptacles on the rear of the UPS.
Vertical |
| Horizontal overlay | ||
| ||||
overlay |
|
| for rack UPS | |
for |
|
|
|
|
|
|
|
| |
tower |
|
|
|
|
UPS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GXT | UPStation GXT | – |
UPStation | – |
|
11. Plug the UPS into a dedicated wall receptacle properly
protected by a circuit breaker
or fuse in accordance with national and local electrical codes. Use a 15 amp rated device for the 500, 700, 1000, or 1500 VA units, 20 amp for the 2000 VA, and 30 amp for the 3000 VA. The wall receptacle must be grounded.
12.Turn ON the UPS by pressing the ON button; then turn on the connected load equipment. The UPS is now providing conditioned power to your equipment.
12 | DISCONTINUED |
| PRODUCT |