Specifications

11.0SPECIFICATIONS

Model Number

 

GXT2-500RT120

 

GXT2-700RT120

GXT2-1000RT120

Model Rating

 

500VA/350W

 

700VA / 490W

 

1000VA / 700W

DIMENSIONS - in. (mm)

 

 

 

 

 

 

Unit

 

3.5 x 21.5 x 17

 

3.5 x 21.5 x 17

 

3.5 x 21.5 x 17

W x D x H

 

(87 x 547 x 430)

 

(87 x 547 x 430)

 

(87 x 547 x 430)

Shipping

 

10.6 x 27.2 x 23

 

10.6 x 27.2 x 23

 

10.6 x 27.2 x 23

W x D x H

 

(269 x 691 x 584)

 

(269 x 691 x 584)

 

(269 x 691 x 584)

WEIGHT - lb. (kg)

 

 

 

 

 

 

Unit

 

48.9 (22.2)

 

48.9 (22.2)

 

49.1 (22.3)

Shipping

 

57.7 (26.2)

 

57.7 (26.2)

 

57.9 (26.3)

INPUT AC PARAMETERS

 

 

 

 

 

Voltage Range (typical)

 

120VAC nominal; variable based on output load

100% - 90% loading

 

80 VAC - 140 VAC

 

80 VAC / 140 VAC

 

80 VAC / 140 VAC

90% -70% loading

 

80 VAC - 140 VAC

 

80 VAC / 140 VAC

 

80 VAC / 140 VAC

70% -30% loading

 

70 VAC - 140 VAC

 

70 VAC / 140 VAC

 

70 VAC / 140 VAC

30% - 0% loading

 

60 VAC - 140 VAC

 

60 VAC / 140 VAC

 

60 VAC / 140 VAC

Frequency

 

40 - 70 Hz; Auto Sensing

Input Power Cord

 

6 ft. attached

 

6 ft. attached

 

10 ft. attached

 

w/ NEMA 5-15 plug

 

w/ NEMA 5-15 plug

 

w/ NEMA 5-15 plug

 

 

 

 

OUTPUT AC PARAMETERS

 

 

 

 

Output Receptacles

 

 

 

(6) NEMA 5-15R

 

Voltage

 

100/110/115/120/127 (user configurable) VAC; ±3%

Frequency

 

 

 

50 Hz or 60 Hz

 

Waveform

 

 

 

Sinewave

 

Main Mode

 

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

Overload

 

 

 

 

 

 

 

BATTERY PARAMETERS

 

 

 

 

 

Type

 

Valve-regulated, nonspillable, lead acid

Qty x V x Rating

 

 

4 x 12V x 7.0 or 7.2 AH

 

Battery Mfg / Part #

 

China Storage Battery / CSB 1270 F2

Backup Time

 

See 13.0 - Battery Run Times

Recharge Time

 

5 hours to 95% capacity after full discharge into 100% load

ENVIRONMENTAL

 

 

 

 

 

 

Operating Temp

 

+32°F to +104°F (0°C to +40°C)

Storage Temp

 

+5°F to +122°F (-15°C to +50°C)

Relative Humidity

 

0% to 95%, non-condensing

Operating Elevation

 

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

Storage Elevation

 

50,000 ft. (15,000m) maximum

Audible Noise

 

<50 dBA, at 1 meter from the rear

 

<45 dBA, at 1 meter from the front or sides

 

 

AGENCY

 

 

 

 

 

 

Safety

 

 

 

UL 1778, c-UL Listed

 

RFI/EMI

 

FCC Part 15, Subpart B, Class A

Surge Immunity

 

IEEE/ANSI C62.41 Category A & B

Transportation

 

 

 

ISTA Procedure 1A

 

32

DISCONTINUED

 

PRODUCT

Page 36
Image 36
Liebert gxt2u user manual Specifications, Model Rating