Troubleshooting

10.0TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the Liebert GXT2U develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.The Fault indicator will illuminate, indicating the UPS detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional load/battery level LED indicators will be illu- minated to provide a diagnostic aid to the operator, as described below:

Fault

E

BYPASS

D

C

UPS ON

 

B BATTERY

A

AC

INPUT

This example shows the UPS

on bypass due to output overload.

A B C D E Fault

AC INPUT BATTERY UPS ON BYPASS

LOAD/BATTERY

LEVEL INDICATORS

LED status

Diagnosis / Audible alarm

All LEDs

On bypass due to output overload; beep every half-second

A LED

On bypass due to overtemperature condition; beep every 4 sec.

B LED

On bypass due to DC bus overvoltage; beep every 4 sec.

C LED

On bypass due to control power supply failure; beep every 4 sec.

D LED

On bypass due to PFC failure; beep every 4 sec.

E LED

On bypass due to inverter failure; beep every 4 sec.

A&C LEDs

UPS failed battery test; long beep every minute

C&E LEDs

UPS shutdown due to command from communication port

(SNMP); no beep

Battery LED

Internal Battery source not available (continuous horn). Check

Flashing

battery connection, completely power down and reboot UPS.

AC LED

Line-to-neutral reversal in the AC input power supply or a loss of

Flashing

proper grounding; continuous horn and UPS will not start.

Bypass LED

Utility power voltage or frequency is out of tolerance; bypass is

Flashing

unavailable.