Battery Cabinet Specifications

12.0BATTERY CABINET SPECIFICATIONS

Model Number

GXT2-48VBATT

GXT2-72VBATT

 

 

 

 

GXT2-500RT120

 

Used With

GXT2-700RT120

 

GXT2-1000RT120

GXT2-3000RT120

UPS Model

GXT2-1500RT120

 

 

 

 

GXT2-2000RT120

 

 

 

 

DIMENSIONS - in. (mm)

 

 

 

 

Unit

3.5 x 21.5 x 17

3.5 x 24.2 x 17

W x D x H

(87 x 547 x 430)

(87 x 618 x 430)

Shipping

10.5 x 27.2 x 23

10.5 x 27.2 x 23

W x D x H

(268 x 692 x 585)

(268 x 692 x 585)

WEIGHT - lb. (kg)

 

 

 

 

 

Unit

65.0 (29.5)

93.6 (42.5)

 

 

 

Shipping

71.1 (32.3)

102.5 (46.5)

 

 

 

BATTERY PARAMETERS

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

 

 

Qty x V x Rating

2 x 4 x 12V x 7.0 or 7.2 AH

2 x 6 x 12V x 9.0 AH

 

 

 

Battery Mfg / Part #

China Storage Battery /

Panasonic / UP-VW1245P1

CSB 1270 F2

Yuasa / REW 45-12

 

Backup Time

See 13.0 - Battery Run Times

 

 

 

ENVIRONMENTAL

 

 

 

 

 

Operating Temp

+32°F to +104°F (0°C to +40°C)

 

 

Storage Temp

+5°F to +122°F (-15°C to +50°C)

 

 

Relative Humidity

0% to 95%, non-condensing

 

 

Operating Elevation

Up to 10,000 ft. (3000m) at 104°F (40°C) without derating

 

 

Storage Elevation

50,000 ft. (15,000 m) maximum

 

 

 

AGENCY

 

 

 

 

 

Safety

UL 1778, c-UL Listed

 

 

RFI/EMI

FCC Part 15, Subpart B, Class A

 

 

Transportation

ISTA Procedure 1A

 

 

 

34