Troubleshooting

Table 1

Troubleshooting guide (continued)

 

 

 

Problem

Cause

Solution

 

 

 

 

 

 

 

Check load level display

Fault and Bypass

 

and remove non-essential

indicator LEDs

UPS overloaded or load

loads. Recalculate the load

and all load level

and reduce number of

equipment is faulty.

LEDs are

 

loads connected to UPS.

 

 

illuminated.

 

 

Check load equipment for

 

 

 

faults.

 

 

 

Ensure UPS is not

 

 

 

overloaded, ventilation

 

 

 

openings not blocked, or

Fault and Bypass

UPS internal fan has a

room ambient temperature

is not excessive. Wait 30

indicator LEDs

problem or UPS shutdown

minutes to allow UPS to

and diagnostic

due to temperature

cool, then restart UPS. If

LED A are

 

condition. Load is on

 

UPS does not restart,

illuminated.

 

bypass power.

 

contact your local dealer,

 

 

 

 

 

 

Liebert representative or

 

 

 

the Liebert Worldwide

 

 

 

Support Group.

Fault and Bypass

 

UPS requires service.

indicator LEDs

UPS internal DC bus

Contact your local dealer,

and diagnostic

Liebert representative or

overvoltage.

LED B are

 

the Liebert Worldwide

 

 

illuminated.

 

 

Support Group.

 

 

 

Fault and Bypass

 

UPS requires service.

indicator LEDs

UPS control power supply

Contact your local dealer,

and diagnostic

Liebert representative or

fault.

LED C are

 

the Liebert Worldwide

 

 

illuminated.

 

 

Support Group.

 

 

 

Fault and Bypass

 

UPS requires service.

indicator LEDs

UPS PFC (Power Factor

Contact your local dealer,

and diagnostic

Liebert representative or

Correction Circuit) fault.

LED D are

 

the Liebert Worldwide

 

 

illuminated.

 

 

Support Group.

 

 

 

Fault and Bypass

 

UPS requires service.

indicator LEDs

 

Contact your local dealer,

and diagnostic

UPS inverter fault.

Liebert Representative or

LED E are

 

 

the Liebert Worldwide

illuminated.

 

 

Support Group.

Fault indicator

 

Replace batteries. Contact

LED and

 

 

your local dealer, Liebert

diagnostic LED A

UPS failed the battery test.

representative or the

and C are

 

 

Liebert Worldwide Support

illuminated.

 

 

Group.