Troubleshooting

Table 1

Troubleshooting guide (continued)

 

 

 

Problem

Cause

Solution

 

 

 

 

 

 

 

Your UPS has received a

 

 

 

signal or command from

 

 

 

the attached computer. If

Fault and Bypass

 

this was inadvertent,

 

ensure the communication

indicator LEDs

UPS shutdown due to a

cable used is correct for

and diagnostic

command from the

your system. For

LED C and E are

communications port(s).

assistance, contact your

illuminated.

 

 

 

 

local dealer, Liebert

 

 

 

 

 

 

representative or the

 

 

 

Liebert Worldwide Support

 

 

 

Group.

 

 

UPS detected a line-to-

 

 

 

neutral reversal or a loss of

 

 

 

proper grounding;

 

 

 

continuous horn and UPS

Contact a qualified

AC LED is

 

will not start.This is active

 

only when power is first

electrician to verify site

flashing.

 

 

applied to the input. Once

wiring.

 

 

 

 

the UPS is running, the AC

 

 

 

LED will not start flashing,

 

 

 

even if the input wiring is

 

 

 

changed.

 

 

 

 

Check battery connections,

 

 

 

completely power down

 

 

 

and restart UPS.

Battery LED is

Battery source is not

NOTE: If the battery circuit

flashing.

 

available; continuous horn.

opens while the UPS is

 

 

 

running, it will be detected

 

 

 

when the next battery test

 

 

 

is performed.

 

 

 

The AC input powers the

 

 

 

PFC input and serves as

 

 

 

the bypass source. If the

 

 

Bypass voltage is present,

AC is present but the

Bypass LED is

but is disabled for use

voltage or frequency

because the voltage or

exceeds the acceptable

flashing.

 

 

frequency is outside

range for safe operation

 

 

 

 

acceptable limits.

with a load, the bypass will

 

 

 

be disabled and this LED

 

 

 

will flash, indicating that the

 

 

 

bypass is unavailable.

30

DISCONTINUED

 

PRODUCT

Page 34