Installation and Commissioning

Figure 10 Bottom plate with cutouts

Sealed Cable Cutout

Network

Cable

Entry

Rear

Cutout for

Water Pipes

Condensed

Water Cutouts

Front

Cable and pipe openings must be sealed air-tight on completion of work.

5.4Condensed Water Connection

If the XDK is operated below dew point, condensed water may occur. As standard there is a water con- nection, 5/8" diameter, in the condensed water tray for drainage.

Preparations for Connecting

Step 1): Remove the air duct

Condensate connection

Step 2): Remove the cap

Step 3.) Connect the nipple with a drain hose 5/8"

Step 4.)

Move and snap the nipple with hose into the hole

When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self- filling siphon with return protection and that the condensate drain is properly sloped.

The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so that air is not drawn into or blown out of the waste pipe.

14

Page 18