Installation and Commissioning
Figure 10 Bottom plate with cutouts
Sealed Cable Cutout
Network
Cable
Entry
Rear
Cutout for
Water Pipes
Condensed
Water Cutouts
Front
Cable and pipe openings must be sealed
5.4Condensed Water Connection
If the XDK is operated below dew point, condensed water may occur. As standard there is a water con- nection, 5/8" diameter, in the condensed water tray for drainage.
Preparations for Connecting
Step 1): Remove the air duct
Condensate connection
Step 2): Remove the cap
Step 3.) Connect the nipple with a drain hose 5/8"
Step 4.)
Move and snap the nipple with hose into the hole
When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self- filling siphon with return protection and that the condensate drain is properly sloped.
The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so that air is not drawn into or blown out of the waste pipe.
14