Operating Conditions
2.0OPERATING CONDITIONS
2.1Proper Application
The XDK is a
NOTE
Under certain conditions, a small amount of heat, (approximately 0.5kW), can escape into the room.
! CAUTION
Risk of improper operation. Can cause equipment damage. For reliable function of the XDK, cold water must be available in the correct amount, and at the correct temperature and pressure. Observe water quality specified in
Table 1 | General operating data |
| |
|
|
| |
Ambient temperature | 50°F to 95°F (10°C to 35°C) | ||
(other temperatures upon request) | |||
|
| ||
Absolute humidity in the installation location | 8g H2O/ kg air maximum | ||
Water temperature, supply | 54°F (12°C); other temperatures upon request | ||
|
| ||
Water temperature, return | 64°F (18°C); other temperatures upon request | ||
|
| ||
Water connection | from below | ||
|
| ||
Condensed water connection | from below | ||
|
| ||
Nominal voltage | 200V to 264V (50Hz and 60 Hz) | ||
|
| ||
Maximum operating pressure | 145 PSI (10 bar) | ||
|
|
|
2