Description
Table 2 | Technical data |
|
|
|
|
| Housing material | Aluminium sheet, sheet steel, galvanized and coated |
|
|
|
| Operating Temperature range | 50°F to 95°F (10°C to 35°C) |
|
|
|
| Abs. atmospheric humidity | 8g / kg maximum |
|
| |
Temperature difference across server | approx. 15K | |
|
|
|
| Noise level | 55 dB(A) sound pressure at a distance of 3 ft. (1m) |
|
|
|
| Useful load | 2204 lb (1000kg) |
|
| |
Cold Water |
| |
|
|
|
| Cooling capacity | 17kW |
|
|
|
| Supply temperature | 54°F (12°C) (other temperatures upon consultation) |
|
|
|
| Return temperature | 64°F to 72°F (18°C to 22°C) (other temperatures upon consultation) |
|
|
|
| Max. operating pressure | 145 PSI (10 bar) |
|
|
|
| Water supply connection | 1" |
|
|
|
3.2.1 Data Overview—XDK
Table 3 | XDK general data |
| |
Nominal Cooling Capacity | 17kW @ 54°F (12°C) EFT | ||
|
| ||
Height, in (mm) | 86.6 (2200) | ||
|
| ||
Width, in (mm) | 31.5 (800) | ||
|
| ||
Depth, in (mm) | 47 (1200) | ||
|
| ||
Usable Height for Electronic | 40 U | ||
Equipment |
| ||
|
| ||
Maximum Electronic | 29 (740) | ||
Equipment Depth, in (mm) | |||
| |||
Electronic Equipment | 68/98 (20/37 | ||
Air Temperature, In/Out, °F (°C) | |||
| |||
Weight, Empty, lb (kg) | 683 (310) | ||
|
| ||
Maximum Weight, Filled | 2,800 (1310) | ||
|
| ||
Maximum Operating | 145 (10) | ||
Water Pressure, psi (bar) | |||
| |||
Water Flow Rate, GPM (m3/h) | 10.7 (2.44) | ||
Water Pressure Drop, psi (bar) | 10 (0.7) | ||
|
| ||
Water Connections, in | 1 | ||
|
| ||
Maximum Air Flow, CFM ( m3/h) | 1800 (3,100) | ||
Sound Pressure Level | 55 dB(A) at 3 ft (1m) | ||
|
| ||
Input Voltage | |||
|
| ||
Maximum Power Draw | 1400W | ||
|
|
| |
Options |
| Leveling Feet or Casters | |
|
|
|
5