Description

3.2Principle of Cooling Operation

Figure 2 Cooling airflow, side view

 

Fan

 

 

Bank

 

Rear

 

Front

of

19" Equipment

of

XDK

XDK

 

 

Air / Water

 

 

Heat Exchanger

 

Cold Water Supply

Side of XDK

Air that has been heated by the servers to 95°F (35°C), for example, is circulated to a specially designed air/water heat exchanger by high-performance fans. The heated air is cooled to 68-77°F (20-25°C) and fed to the front of the server.

The server fans can draw in the air and feed it over internal components. Cold water is provided by a separate Liebert XD Pumping unit.

A condensate tray with a 5/8" outlet is below the heat exchanger.

NOTE

If the rear door (with fans) is opened, the front door must be opened. If the front door is opened, it is not necessary to open the rear door.

4

Page 8
Image 8
Liebert XDK user manual Principle of Cooling Operation, Air / Water, Heat Exchanger