MODEL BGUS/BGUS-DSG/SG-D OPERATOR INSTALLATION GUIDE

TERMINAL CONNECTION DESCRIPTIONS

TERMINALS

FUNCTION

DESCRIPTION OF FUNCTION

24VAC

24VAC

Provides 24Volt AC power for accessories.

24VAC N

 

Note: DC models will NOT have 24Volt AC power available.

24VDC+

24VDC

Provides 24Volt DC power for accessories.

24VDC- COMM.

 

 

1

& 4

OPEN

Opens the operator. Several accessories such as button stations, keypads,

 

 

 

transmitters and card readers can be wired to open.

3

& 4

CLOSE

Closes the operator. Use caution when wiring accessories to these terminals. The

 

 

 

gate must be clearly visible from the location of any accessories wired to

 

 

 

close.

4

& 5

SINGLE-BUTTON

Performs the single-button function which will alternate between open and close

 

 

 

or open, stop and close - depending on dip switch #3. (See Page 9 for details.)

2

& 4

STOP

Stops the operator. On barrier gate operators, this button is also the reset

 

 

 

button.

4

& 6

REVERSE

This function will cause a reversal when the gate is traveling closed and will travel

 

 

 

back to the fully open position. Loop detectors are often wired for reverse.

4

& 50

OPEN/RESET

A signal across these terminals will cause the arm of the barrier gate operator to

 

 

 

raise and stay open until the signal is gone, at which point the arm will immediately

 

 

 

begin to come down.

4

& 51

CLOSE

This function works only while the arm is coming down. Any signal to this function

 

 

OBSTRUCTION

will cause the arm to stop and fully reverse.

4

& 11

RESET

This function will cause the arm to come down as soon as the signal clears.

24VDC+ & 60

RUN

A 24Volt DC device such as a strobe light or alarm can be wired to these terminals.

 

 

 

These devices will be powered while the motor is running. (See Page 9 for

 

 

 

details.)

You must follow all required safety precautions and instructions at all times. Review the safety brochure included with the operator. If any pages are missing or unreadable, contact LINEAR at 1-800-333-1717 to request additional copies.

Controls intended for user activation must be located at least six feet (6’) away from any moving part of the gate and where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or easily accessible controls shall have a security feature to prevent unauthorized use.

Do not adjust the circuit board current sensing feature too high. It should be adjusted high enough to keep the gate arm from falsely triggering the sensing, but no higher than necessary for the barrier gate to operate. Do not defeat the purpose of this function!