MODEL BGUS/BGUS-DSG/SG-D OPERATOR INSTALLATION GUIDE

BGUS-DSG-D

CHARGER BOARD SLEEP MODE

When primary AC power is not available, the operator will continue to operate in battery only mode if the charger board is set in its RUN mode (see Battery Backup Charger Configuration). Accessories wired into the operator will continue to draw power, even when the operator is not opening or closing the gate. This can dramatically reduce the amount of standby time available from the batteries.

To extend the available standby time, the charger board has a “sleep” mode feature which will turn off power to all controls except for any that are wired according to the schematics below. By removing the black jumper cap JP1 located in the upper right hand corner of the charger board this feature can be enabled. After fifteen minutes of inactivity, all controls except those wired as shown below will turn off. Those wired as shown will continue to have power at all times and will upon activation generate first a “wake” signal that will power all controls back up, and then create either an open signal or single button signal, depending on how the wire jumper shown below is connected.

 

JP1

 

OPEN

JUMPER CAP

WAKE

 

TERMINAL

 

TERMINAL

CHARGER BOARD

 

 

-13-

Page 13
Image 13
Linear manual Model BGUS/BGUS-D SG/SG-D Operator Installation Guide, Charger Board Sleep Mode